C-2
Parameter Reference
AC30 series Variable Speed Drive
Active Front End (AFE)
Control Screen
Setup:: Regen Control
Monitor:: Regen Control
Active Front End (AFE) is a mode of operation of the drive required for full 4-Q regeneration capabilities. AFE control mode allows a single
AC30P/AC30D drive to act as a 4-Q power supply unit that is capable of drawing (motoring) and supplying (regenerating) sinusoidal, near-unity
power factor current from the supply. The output from the 4-Q Regen drive acts as a DC supply which is used to power other drives on a common
DC Bus system.
AFE Control Mode is available as a standard option in the AC30P/AC30D firmware, however set-up and installation requirements need to be
adhered to in order to use a drive as 4-Q regen unit. These requirements are described in more detail in the paragraphs that follow.
Hardware Requirements
The figure below shows the typical installation configuration of the drive operating in AFE control mode.
Optional EMC
Filter
-
U (M1)
V (M2)
W (M3)
DC +
DC +
W
V
U
W
V
U
DC Link Fuses
LCL Filter
3 – ph
Supply
3 – ph
Input
Contactor
AC30P 4-Q
Line Fuses
External Pre-charge
DC -
Common DC Link
3 – ph
Output
Contactor
DC -
DC +
DC -
AC30
AC30
Motor
Motor
Encoder Option Card
7004-04-00
Line sync card
LA471892U001
Summary of Contents for AC30 series
Page 4: ...AC30 series Variable Speed Inverter...
Page 18: ...3 4 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames G H J...
Page 19: ...Product Overview 3 5 AC30 series Variable Speed Inverter Block Diagram for Frame K...
Page 20: ...3 6 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames L N...
Page 22: ...3 8 Product Overview AC30 series Variable Speed Inverter...
Page 65: ...6 27 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Scoping Drive Parameters...
Page 66: ...6 28 Setup Wizard AC30 series Variable Speed Inverter...
Page 84: ...7 18 Trips Fault Finding AC30 series Variable Speed Inverter...
Page 122: ...9 6 Fire Mode AC30 series Variable Speed Drive...
Page 188: ...C 6 Parameter Reference AC30 series Variable Speed Drive...
Page 189: ...Parameter Reference C 7 AC30 series Variable Speed Drive...