Fieldbuses
A-33
AC30 series Variable Speed Inverter
Inverter Configuration
Enabling
To enable the PROFINET IO device set the parameter
3132 PROFINET Enable
to
TRUE
. Note the PROFINET IO device will only operate when
the inverter is the Operational state.
The current state of the PROFINET IO device is given by the parameter
3143 PROFINET State
.
Station Name
A station name must be assigned to the PROFINET device. This is set using a PROFINET configuration program. Typically this is done from
within the PC program used to program the PROFINET PLC. The station name is stored in non-volatile memory within the inverter.
The station name should consist of only alpha-numeric, period (.) and hyphen (-) characters. The diagnostic parameter
3136 PROFINET Station
Name
shows the first 21 characters of the station name.
Update Time
The cyclic I/O update time is set by the PLC. Update times allowed are calculated by multiples (8, 16, …, 512) of the send clock (1ms). Thus the
lowest update time is
8ms
. However due to constraints in the inverter the update time is further restricted by the switching frequency, as given in
the table below.
Note:
If an update time that exceeds the restrictions is attempted then
a connection by the PLC will be rejected by the inverter
and the
parameter
3144 PROFINET Diagnostic
will be in the
CONNECTION REJECTED
state.
It is recommended to increase the update time for larger mapped cyclic I/O data.
Minimum I/O Update Time
Switching Frequency
2-4kHz
4-6kHz
6-8kHz
8-10kHz
Induction motor control
8ms
8ms
16ms
32ms
PMAC motor control
8ms
16ms
32ms
Not permitted
Summary of Contents for AC30 series
Page 4: ...AC30 series Variable Speed Inverter...
Page 18: ...3 4 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames G H J...
Page 19: ...Product Overview 3 5 AC30 series Variable Speed Inverter Block Diagram for Frame K...
Page 20: ...3 6 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames L N...
Page 22: ...3 8 Product Overview AC30 series Variable Speed Inverter...
Page 65: ...6 27 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Scoping Drive Parameters...
Page 66: ...6 28 Setup Wizard AC30 series Variable Speed Inverter...
Page 84: ...7 18 Trips Fault Finding AC30 series Variable Speed Inverter...
Page 122: ...9 6 Fire Mode AC30 series Variable Speed Drive...
Page 188: ...C 6 Parameter Reference AC30 series Variable Speed Drive...
Page 189: ...Parameter Reference C 7 AC30 series Variable Speed Drive...