C-4
Parameter Reference
AC30 series Variable Speed Drive
AFE inductance parameter must be set to the value of the total line choke inductance.
AFE VDC Demand parameter sets the required DC link voltage for the common DC link bus. Recommended level for nominal drive voltage rating of
400V (with 820V overvoltage trip level and 410V undervoltage trip level) is 720V.
AFE VDC Min Level parameter defines the level of DC link voltage at which external precharge closure is instigated. By default it is equal to
undervoltage trip level.
For any additional adjustments (if required) the full set of the AFE related parameters can be found in the
Parameters::Regen Control::AFE
menu.
Other (
non-AFE
) drives, supplied through common DC bus
MUST
have the following set-up:
DC Link volts limit feature disabled
If in V/Hz mode the Terminal Voltage Mode parameter set to FIXED
Summary of Contents for AC30 series
Page 4: ...AC30 series Variable Speed Inverter...
Page 18: ...3 4 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames G H J...
Page 19: ...Product Overview 3 5 AC30 series Variable Speed Inverter Block Diagram for Frame K...
Page 20: ...3 6 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames L N...
Page 22: ...3 8 Product Overview AC30 series Variable Speed Inverter...
Page 65: ...6 27 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Scoping Drive Parameters...
Page 66: ...6 28 Setup Wizard AC30 series Variable Speed Inverter...
Page 84: ...7 18 Trips Fault Finding AC30 series Variable Speed Inverter...
Page 122: ...9 6 Fire Mode AC30 series Variable Speed Drive...
Page 188: ...C 6 Parameter Reference AC30 series Variable Speed Drive...
Page 189: ...Parameter Reference C 7 AC30 series Variable Speed Drive...