A-12
Fieldbuses
AC30 series Variable Speed Inverter
Inverter Configuration
Enabling
To enable the EtherNet/IP adapter set the parameter
3128 EtherNet IP Enable
to TRUE.
The current state of the EtherNet/IP adapter is given by the parameter
3130 EtherNet IP State
.
Note the EtherNet/IP adapter is only active when the inverter is in the Operational state.
IP Settings
The IP settings are set up from the inverter using the Ethernet parameters described in Chapter 12. The IP settings of the inverter cannot be set
via the PLC.
The current IP settings are monitored using the parameters:
0926 IP Address
0927 Subnet Mask
0928 Gateway Address
If parameter
0929 DHCP
is set to TRUE, then the IP address will be set from the DHCP server on the network, if one is available.
If parameter
0930 Auto IP
is set to TRUE, then the IP address will be automatically be assigned a link-local address.
If both parameters
0929 DHCP
and
0930 Auto IP
are FALSE, then the IP address, subnet mask and gateway address will be set from the values
in the parameters:
0933 User IP Address
0934 User Subnet Mask
0935 User Gateway Address
Summary of Contents for AC30 series
Page 4: ...AC30 series Variable Speed Inverter...
Page 18: ...3 4 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames G H J...
Page 19: ...Product Overview 3 5 AC30 series Variable Speed Inverter Block Diagram for Frame K...
Page 20: ...3 6 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames L N...
Page 22: ...3 8 Product Overview AC30 series Variable Speed Inverter...
Page 65: ...6 27 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Scoping Drive Parameters...
Page 66: ...6 28 Setup Wizard AC30 series Variable Speed Inverter...
Page 84: ...7 18 Trips Fault Finding AC30 series Variable Speed Inverter...
Page 122: ...9 6 Fire Mode AC30 series Variable Speed Drive...
Page 188: ...C 6 Parameter Reference AC30 series Variable Speed Drive...
Page 189: ...Parameter Reference C 7 AC30 series Variable Speed Drive...