Panduit VerySafe VS2-AVT Series Instruction Manual Download Page 9

June 2022 

VeriSafe 2.0 AVT 

Schematics

WARNING:

 

„

The AVT must be installed correctly and grounded as described in this Instruction Manual to provide proper indication of 

absence of voltage . Sensor leads must not be mechanically connected with each other for the device to verify connection 

to the circuit . Correct function of the device must be verified after installation, see Commissioning Checklist section, p . 14 . 

Failure to comply with these instructions could result in product failure, injury or death .

 

„

Sensor leads of the same labeled set (i .e .; L1, L2, L3 and GND) should be terminated on the same conductor .  Each 

conductor should have at least one sensor lead set, as shown on the schematic diagrams .

THREE-PHASE DELTA

 THREE-PHASE DELTA:  3 WIRE + PE 

L3

L1

L2

L3

L2

L1

GND

Isolation Module

Enclosure

External

System

Green / Yellow

L1

L2

L3

 HIGH-LEG DELTA:  3 WIRE + N PE 

L3

L1

L2

L3

L2

L1

GND

Isolation Module

Enclosure

External

System

Green / Yellow

L1

L2

L3

Neutral

 CORNER GROUNDED DELTA:  3 WIRE + PE 

L3

L1

L2

L2

L1

GND

Isolation Module

Enclosure

External

System

Green / Yellow

L1

L2

L3

L3

THREE-PHASE WYE

 THREE-PHASE WYE:  3 WIRE + PE (NO NEUTRAL)

L3

L1

L2

L3

L2

L1

GND

Isolation Module

Enclosure

External

System

Green / Yellow

L1

L2

L3

 THREE-PHASE WYE:  3 WIRE + NEUTRAL AND PE 

L3

L1

L2

L3

L2

L1

GND

Isolation Module

Enclosure

External

System

Green / Yellow

L1

L2

L3

Neutral

 THREE-PHASE WYE HIGH RESISTANCE GROUND:  

3 WIRE + NEUTRAL AND PE 

L3

L1

L2

L3

L2

L1

GND

Isolation Module

Enclosure

External

System

Green / Yellow

L1

L2

L3

Neutral

SINGLE-PHASE

 SINGLE-PHASE:  2 WIRE + PE

L1

N

L2

L1

GND

Isolation Module

Enclosure

External

System

Green / Yellow

L1

L2

  SINGLE-PHASE:  2 WIRE + FLOATING GROUND 

L1

N

L2

L1

GND

Isolation Module

Enclosure

External

System

Green / Yellow

L1

L2

  SINGLE-PHASE:  3 WIRE + PE 

L1

L2

N

L2

L1

GND

Isolation Module

Enclosure

External

System

Green / Yellow

L1

L2

continued on next page

Summary of Contents for VerySafe VS2-AVT Series

Page 1: ...Support Safety Information 2 Informations relatives la s curit 3 System Configuration 4 5 Components 4 Part Number Identification 4 Power for AVT Test 4 DC Power Input 4 Indicator Module 5 Absence of...

Page 2: ...standards The battery powered indicator module contains a lithium battery that is a fire explosion and severe burn hazard Do not crush recharge disassemble or heat above 85 C 185 F incinerate or expos...

Page 3: ...ient une pile au lithium qui pr sente un risque d incendie d explosion et de br lures graves Ne pas craser recharger d monter incin rer ou chauffer la pile plus de 85 C 185 F ni exposer son contenu l...

Page 4: ...h or without the network module 10 100 PoE IEEE 802 3af Type 1 Class III PoE topology Refer to network module instruction manual available at www panduit com DC POWER INPUT The 2 0 AVT includes an opt...

Page 5: ...ndicator module can be used in the AUX port however the battery will not have any impact on powering the AVT ABSENCE OF VOLTAGE OUTPUTS The AVT includes a set of redundant isolated transistor outputs...

Page 6: ...d 3 V See the Installation Considerations section for additional information Overvoltage Category III 1000 V IV 600 V Degree of Protection Indicator Module for flat surface mounting in a TYPE UL NEMA...

Page 7: ...fications UL 1436 Standard for outlet circuit testers and similar indicating devices CAN CSA C22 2 No 160 Voltage and polarity testers IEC UL CSA C22 2 NO 61010 1 IEC UL CSA C22 2 NO 61010 2 030 Safet...

Page 8: ...ation Flashes Description 1 2 4 5 6 7 or 8 Check Battery Voltage above Threshold Installation Not Verified See User Manual 3 Temperature Out of Range See Diagnostic Code for Status VERISAFE 2 0 Absenc...

Page 9: ...IGH LEG DELTA 3 WIRE NEUTRAL PE L3 L1 L2 L3 L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 L3 Neutral CORNER GROUNDED DELTA 3 WIRE PE L3 L1 L2 L2 L1 GND Isolation Module Enclo...

Page 10: ...L2 Ground Bond DC SYSTEM POSITIVE GROUND DC DC L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 Ground Bond DC SYSTEM 3 WIRE CENTER GROUND DC DC L2 L1 GND Isolation Module Enclo...

Page 11: ...e via a tap to the circuit conductor using connectors terminal strips or power distribution blocks etc which are rated for the application It is generally preferred to use connection methods that DO N...

Page 12: ...MODULE NETWORK MODULE DIN RAIL MOUNTING Snap the Isolation Module onto the DIN rail OR SURFACE MOUNTING Mount the isolation module to any surface using four 6 M3 5 pan head screws or another compatib...

Page 13: ...sure that contains the isolation mod ule the system cable must be installed in a conduit When installed in conduit the system cable should be regarded as a data cable and must not use the same conduit...

Page 14: ...mechanically connected to each other Instruction label Verify that a label is placed near each indicator module and marked to indicate where the AVT is installed Record changes to panel documentation...

Page 15: ...e the test has failed and flashes after a solid il lumination to indicate the reason for failure see Troubleshooting section for additional information VOLTAGE PRESENCE INDICATORS The red indicators i...

Page 16: ...s a stored energy source wait several minutes then re test to see if energy has dissipated 3 Temperature out of range Verify that the temperature of the isolation module is within the acceptable range...

Page 17: ...module to ensure the retention nut is tight and cap is firmly in place CLEANING INSTRUCTIONS The indicator module can be cleaned with a damp cloth or isopropyl alcohol based cleaner Do not use abrasi...