Panduit VerySafe VS2-AVT Series Instruction Manual Download Page 13

June 2022 

13 

VeriSafe 2.0 AVT 

INDICATOR MODULE AND INSTRUCTION LABEL

NOTE:

  The Instruction Label is UL approved for application to galvanized and stainless steel, ABS, polycarbonate, and polyester paint-

ed surfaces . It is up to the installer to verify proper bond to other surface types .

+

-

Cap

Indicator

Module 

Body

Gasket

Battery

Instruction Label

Panel Nut

SYSTEM CABLE

1. 

Insert the end of the system cable with the right-angle connector in the back of the indicator module .  Press firmly into the open-

ing until you feel it latch . Pull back on the connector to verify that it has properly latched .

2. 

Insert the keyed-end of the system cable into the isolation module port labeled INDICATOR .  System cable for an additional indica-

tor (optional) may be inserted into the isolation module port labeled AUX .

 

„

The system cable must be separated from the sensor leads and other circuits in the 

electrical enclosure by a minimum of 0 .25 inches (6 mm) .

 

„

The maximum allowable system cable length for the INDICATOR port is 30 ft (9 .1m) .

 

„

The maximum allowable system cable length for AUX port is 500 ft (152m) .

 

„

If the system cable is routed outside of the enclosure that contains the isolation mod-

ule, the system cable must be installed in a conduit .  When installed in conduit, the 

system cable should be regarded as a data cable and must not use the same conduit as 

the electrical power conductors .

Battery Powered

Battery Free

BATTERY POWERED INDICATOR MODULE

1. 

Tighten the panel nut until both it and the 

gasket make full contact with the enclosure 

surface . Then, tighten an additional 1/4 turn .

2. 

Install battery into battery tray .  The positive 

terminal should face the operator .  Ensure the 

battery is fully seated before proceeding .  See 

Battery Replacement section for details .

3. 

Install instruction label near the indicator 

module on the exterior of the enclosure .  

Mark the label to indicate where in the circuit 

the AVT is installed .

4. 

Install the cap label with the appropriate 

language, if other than English .

BATTERY FREE INDICATOR MODULE

1. 

Tighten the panel nut until both it and the 

gasket make full contact with the enclosure 

surface . Then, tighten an additional 1/4 turn .

2. 

Install instruction label near the indicator 

module on the exterior of the enclosure .  

Mark the label to indicate where in the circuit 

the AVT is installed .

3. 

Install the cap label with the appropriate 

language, if other than English .

Indicator

Module

Faceplate

Instruction Label

Indicator

Module 

Housing

Panel 

Nut

Gasket

Summary of Contents for VerySafe VS2-AVT Series

Page 1: ...Support Safety Information 2 Informations relatives la s curit 3 System Configuration 4 5 Components 4 Part Number Identification 4 Power for AVT Test 4 DC Power Input 4 Indicator Module 5 Absence of...

Page 2: ...standards The battery powered indicator module contains a lithium battery that is a fire explosion and severe burn hazard Do not crush recharge disassemble or heat above 85 C 185 F incinerate or expos...

Page 3: ...ient une pile au lithium qui pr sente un risque d incendie d explosion et de br lures graves Ne pas craser recharger d monter incin rer ou chauffer la pile plus de 85 C 185 F ni exposer son contenu l...

Page 4: ...h or without the network module 10 100 PoE IEEE 802 3af Type 1 Class III PoE topology Refer to network module instruction manual available at www panduit com DC POWER INPUT The 2 0 AVT includes an opt...

Page 5: ...ndicator module can be used in the AUX port however the battery will not have any impact on powering the AVT ABSENCE OF VOLTAGE OUTPUTS The AVT includes a set of redundant isolated transistor outputs...

Page 6: ...d 3 V See the Installation Considerations section for additional information Overvoltage Category III 1000 V IV 600 V Degree of Protection Indicator Module for flat surface mounting in a TYPE UL NEMA...

Page 7: ...fications UL 1436 Standard for outlet circuit testers and similar indicating devices CAN CSA C22 2 No 160 Voltage and polarity testers IEC UL CSA C22 2 NO 61010 1 IEC UL CSA C22 2 NO 61010 2 030 Safet...

Page 8: ...ation Flashes Description 1 2 4 5 6 7 or 8 Check Battery Voltage above Threshold Installation Not Verified See User Manual 3 Temperature Out of Range See Diagnostic Code for Status VERISAFE 2 0 Absenc...

Page 9: ...IGH LEG DELTA 3 WIRE NEUTRAL PE L3 L1 L2 L3 L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 L3 Neutral CORNER GROUNDED DELTA 3 WIRE PE L3 L1 L2 L2 L1 GND Isolation Module Enclo...

Page 10: ...L2 Ground Bond DC SYSTEM POSITIVE GROUND DC DC L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 Ground Bond DC SYSTEM 3 WIRE CENTER GROUND DC DC L2 L1 GND Isolation Module Enclo...

Page 11: ...e via a tap to the circuit conductor using connectors terminal strips or power distribution blocks etc which are rated for the application It is generally preferred to use connection methods that DO N...

Page 12: ...MODULE NETWORK MODULE DIN RAIL MOUNTING Snap the Isolation Module onto the DIN rail OR SURFACE MOUNTING Mount the isolation module to any surface using four 6 M3 5 pan head screws or another compatib...

Page 13: ...sure that contains the isolation mod ule the system cable must be installed in a conduit When installed in conduit the system cable should be regarded as a data cable and must not use the same conduit...

Page 14: ...mechanically connected to each other Instruction label Verify that a label is placed near each indicator module and marked to indicate where the AVT is installed Record changes to panel documentation...

Page 15: ...e the test has failed and flashes after a solid il lumination to indicate the reason for failure see Troubleshooting section for additional information VOLTAGE PRESENCE INDICATORS The red indicators i...

Page 16: ...s a stored energy source wait several minutes then re test to see if energy has dissipated 3 Temperature out of range Verify that the temperature of the isolation module is within the acceptable range...

Page 17: ...module to ensure the retention nut is tight and cap is firmly in place CLEANING INSTRUCTIONS The indicator module can be cleaned with a damp cloth or isopropyl alcohol based cleaner Do not use abrasi...

Page 18: ...CATOR MODULE For the battery free indicator module order Panduit SKU VS2 AVT GASKET for gasket replacement kit 1 Unplug the system cable and remove the panel nut 2 Squeeze the top and bottom of the ho...

Page 19: ...r 4 No Warranty for Third Party Products Panduit makes no representations and disclaims all warranties of any kind express or implied relative to any third party product or services including any thir...