VeriSafe 2.0 AVT
6
June 2022
Technical Specifications
WARNING
:
Do
not use this product outside of the specified performance and environmental limits .
Failure to comply with
these specifications could result in product failure, personal injury, or death.
WARNING
:
The VeriSafe 2 .0 AVT is designed for use in 50 or 60Hz AC electrical systems and DC electrical systems . The AVT
should not be installed on sections of a circuit where the AVT is exposed to high frequency energy such as variable frequency
drives (VFD) or other circuit elements generating high frequency energy (waveforms exhibiting high Electro-Magnetic Inter-
ference (EMI)) . For more information on where to position the VeriSafe 2 .0 AVT in VFD applications, see the Technical Note
available on Panduit .com .
Environmental Ratings
Operating Temperature
-25°C to 60°C (-13°F to 140°F)
Storage Temperature
-45°C to 85°C (-49°F to 185°F)
Humidity
5 to 90% non-condensing; Rated 80% at 40°C (104°F), decreasing linearly to 50% at 60°C (140°F)
Pollution Degree
3 (Ordinary Locations); 2 (see Hazardous Locations Table for special requirements)
Altitude
Up to 5000 meters (16400 feet)
Applications
Electrical System
For use in 3-phase AC systems, single-phase AC systems and DC systems
Voltage Detection Range
Up to 1000 VAC (50 or 60 Hz), 1000 VDC
Absence of Voltage Threshold 3 V (See the Installation Considerations section for additional information)
Overvoltage Category
III (1000 V), IV (600 V)
Degree of Protection
Indicator Module: for flat surface mounting in a TYPE (UL, NEMA and CSA) 1, 12, 13, 4, 4X, IP66,
IP67 or IP69 enclosure . Verify that the seal, o-rings and gaskets are clean to ensure proper sealing .
Isolation Module: Open Type, IP20 .
Hazardous Locations
Special Conditions
of Use
The equipment shall be installed in an enclosure that provides a degree of protection not less than
IP 54 in accordance with IEC 60079-0 .
The enclosure must only be accessible with use of a tool .
Certificate Numbers
(Hazardous Locations)
ATEX: UL 22 ATEX 2608X
IECEx: IECEx UL22 .0094X
UKEx: UKEX UL22UKEX2482X
Isolation Module
(Hazardous Location Ratings)
cULus: Class I, Division 2, Groups A, B, C, D
Class I Zone 2 AEx ec IIC T5 Gc; Ex ec T5 Gc
ATEX: II 3G Ex ec IIC T5 Gc
IECEx: Ex ec IIC T5 Gc
Voltage Indicator Modules
(Hazardous Location Ratings)
cULus: Class I, Division 2, Groups A, B, C, D
Class II, Division 2, Groups F and G
Class I Zone 2 AEx ic ec IIC T6 Gc; Ex ic ec IIC T6 Gc
Zone 22 AEx tc IIIC T68°C Dc; Ex tc IIIC T68°C Dc
ATEX:
II 3G Ex ic ec IIC T6 Gc
II 3D Ex tc IIIC T68°C Dc
IECEx: Ex ic ec IIC T6 Gc
Ex tc IIIC T68°C Dc
Power Requirements
Battery
Industrial 3 .6 V Lithium . Refer to Maintenance section for list of approved batteries .
Auxiliary (DC) Power
35 mA max @ 12 VDC; 17 mA max @ 24 VDC
Power over EtherNet (PoE)
PoE (10/100), 15 mA, IEEE 802 .at (-af) Type 1 Class III PoE topology