VeriSafe 2.0 AVT 

Installation Considerations

This section provides guidelines for installing the 2 .0 AVT . It also addresses common application scenarios and describes best practices .

GENERAL INFORMATION 

Before installing the AVT, identify all sources of electrical energy in the equipment . Install the AVT at the point in the circuit 

where you would normally test for voltage . The AVT will only test for voltage at the point where it is installed . If there are multi-

ple energy sources or multiple test points, consider using multiple AVTs .  Mark the test location on the yellow instruction label . 

Apply this label to outside of enclosure near the indicator module . There should not be any circuit elements (ex . circuit breaker, 

fuse, VFD, switch or similar control devices, etc .) installed between each pair of sensor leads .  Although the absence of voltage 

threshold is 3 .0 V, residual voltages should be less than 2 .7 V to ensure proper function . 

EFFECT ON SHORT CIRCUIT CURRENT RATING (SCCR)

AVTs listed to UL 1436 are required to operate as a secondary circuit that is isolated from the circuit conductors by use of a 

transformer, optical isolator, or limiting impedance, or other similar means . This is intended to reduce the risks of both electric 

shock and thermal hazard . These isolation circuits allow very limited current flow, if any, through the AVT . 
The VeriSafe 2 .0 AVT is suitable for use on circuits delivering up to 300,000 rms symmetrical A at 1000

 

V .

AVT sensor lead terminations should be made via a tap to the circuit conductor using connectors, terminal strips, or power 

distribution blocks, etc . which are rated for the application . It is generally preferred to use connection methods that DO NOT 

pierce or otherwise compromise the integrity of the conductor . Connectors that require conductors to be cut or spliced can be 

used but may limit the SCCR .

USE OF OVERCURRENT PROTECTION

Installation of an AVT with overcurrent protection is neither required nor recommended . UL 1436 requires AVTs to be construct-

ed so that internal component failures will not expose the AVT to available short circuit currents from the main power supply 

during normal operation and under single-fault conditions . The 2 .0 AVT uses high impedance to limit voltage and current flow 

through the device to safe levels . In addition, the AVT has been tested to withstand transient overvoltage up to 8 kV .

If the AVT sensor leads are not longer than 

10 feet, they can be treated as a feeder 

circuit and do not require overcurrent 

protection [NFPA 70:2020 240 .21(B)(1)(b) 

Exception and CSA C22 .1:21 14-100(b)]

In certain regions and countries, additional overcurrent protection is required to 

conform to standards such as AS/NZS3000 . Do not install multiple sensor leads 

on one overcurrent protection device .  Sensor lead pairs must not be electrically 

connected in the event that the overcurrent protection is in the open state .  Do not 

install overcurrent protection on the two green ground leads . 

GND

L3

L2

L1

DISCONNECT

VeriSafe Isolaon

Module

L1 L1

L2

L3

L2

L3

PE

GND

L3

L2

L1

DISCONNECT

VeriSafe Isolaon

Module

L1 L1

L2

L3

L2

L3

PE

F1 F2

F3 F4

F5 F6

   

GND

L3

L2

L1

DISCONNECT

VeriSafe Isolaon

Module

L1 L1

L2

L3

L2

L3

PE

F1

F2

F3

Summary of Contents for VerySafe VS2-AVT Series

Page 1: ...Support Safety Information 2 Informations relatives la s curit 3 System Configuration 4 5 Components 4 Part Number Identification 4 Power for AVT Test 4 DC Power Input 4 Indicator Module 5 Absence of...

Page 2: ...standards The battery powered indicator module contains a lithium battery that is a fire explosion and severe burn hazard Do not crush recharge disassemble or heat above 85 C 185 F incinerate or expos...

Page 3: ...ient une pile au lithium qui pr sente un risque d incendie d explosion et de br lures graves Ne pas craser recharger d monter incin rer ou chauffer la pile plus de 85 C 185 F ni exposer son contenu l...

Page 4: ...h or without the network module 10 100 PoE IEEE 802 3af Type 1 Class III PoE topology Refer to network module instruction manual available at www panduit com DC POWER INPUT The 2 0 AVT includes an opt...

Page 5: ...ndicator module can be used in the AUX port however the battery will not have any impact on powering the AVT ABSENCE OF VOLTAGE OUTPUTS The AVT includes a set of redundant isolated transistor outputs...

Page 6: ...d 3 V See the Installation Considerations section for additional information Overvoltage Category III 1000 V IV 600 V Degree of Protection Indicator Module for flat surface mounting in a TYPE UL NEMA...

Page 7: ...fications UL 1436 Standard for outlet circuit testers and similar indicating devices CAN CSA C22 2 No 160 Voltage and polarity testers IEC UL CSA C22 2 NO 61010 1 IEC UL CSA C22 2 NO 61010 2 030 Safet...

Page 8: ...ation Flashes Description 1 2 4 5 6 7 or 8 Check Battery Voltage above Threshold Installation Not Verified See User Manual 3 Temperature Out of Range See Diagnostic Code for Status VERISAFE 2 0 Absenc...

Page 9: ...IGH LEG DELTA 3 WIRE NEUTRAL PE L3 L1 L2 L3 L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 L3 Neutral CORNER GROUNDED DELTA 3 WIRE PE L3 L1 L2 L2 L1 GND Isolation Module Enclo...

Page 10: ...L2 Ground Bond DC SYSTEM POSITIVE GROUND DC DC L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 Ground Bond DC SYSTEM 3 WIRE CENTER GROUND DC DC L2 L1 GND Isolation Module Enclo...

Page 11: ...e via a tap to the circuit conductor using connectors terminal strips or power distribution blocks etc which are rated for the application It is generally preferred to use connection methods that DO N...

Page 12: ...MODULE NETWORK MODULE DIN RAIL MOUNTING Snap the Isolation Module onto the DIN rail OR SURFACE MOUNTING Mount the isolation module to any surface using four 6 M3 5 pan head screws or another compatib...

Page 13: ...sure that contains the isolation mod ule the system cable must be installed in a conduit When installed in conduit the system cable should be regarded as a data cable and must not use the same conduit...

Page 14: ...mechanically connected to each other Instruction label Verify that a label is placed near each indicator module and marked to indicate where the AVT is installed Record changes to panel documentation...

Page 15: ...e the test has failed and flashes after a solid il lumination to indicate the reason for failure see Troubleshooting section for additional information VOLTAGE PRESENCE INDICATORS The red indicators i...

Page 16: ...s a stored energy source wait several minutes then re test to see if energy has dissipated 3 Temperature out of range Verify that the temperature of the isolation module is within the acceptable range...

Page 17: ...module to ensure the retention nut is tight and cap is firmly in place CLEANING INSTRUCTIONS The indicator module can be cleaned with a damp cloth or isopropyl alcohol based cleaner Do not use abrasi...

Page 18: ...CATOR MODULE For the battery free indicator module order Panduit SKU VS2 AVT GASKET for gasket replacement kit 1 Unplug the system cable and remove the panel nut 2 Squeeze the top and bottom of the ho...

Page 19: ...r 4 No Warranty for Third Party Products Panduit makes no representations and disclaims all warranties of any kind express or implied relative to any third party product or services including any thir...

Reviews: