Panduit VerySafe VS2-AVT Series Instruction Manual Download Page 4

VeriSafe 2.0 AVT  

June 2022

System Configuration

COMPONENTS

1

2

3

2

3

4

Isolation Module
System Cable
Indicator Module 

3.6V Battery Powered option shown 

Battery Free option available

Instruction Label 

Place a Label for 

each Indicator used

1

2

4

3

Flashing - Test in Progress

Solid - Voltage may be Present

Equipment De-Energized, < 3V

Push Button to Begin Test

Hazardous Voltage Present

Line

   

Load

   

Other 

_________

Tester location:

   

# Flashes

Description

1
2

4

5, 6, 7 or 8

Check Battery
Voltage above Threshold

Installation Not Verified
See User Manual

3

Temperature Out of Range

See Diagnostic Code for Status: 

V

ERI

S

AFE 2.0

Absence of Voltage Tester

CAT IV (1000V), CAT IV (600V)

 

_________

 

 

Follow safety
procedures &

use required PPE

2.65

[67.3]

3.20

[81.3]

PART NUMBER IDENTIFICATION

VS2-AVT-XYZ-##

VS2-AVT

XY

 Power System

Z

 Indicator

##

  System Cable

VeriSafe 2 .0 AVT

3P

 = Three-Phase System 

1P

 = Single-Phase / DC System

F

 = Battery Free Indicator 

B

 = Battery Powered Indicator

02

 = 2’ (0 .6m) System Cable 

08

 = 8’ (2 .4m) System Cable 

16

 = 16’ (4 .8m) System Cable

NOTE:

  Accessories are available for the VS2-AVT, refer to www .panduit .com .

POWER FOR AVT TEST

Battery

Auxiliary DC

Power over Ethernet (PoE)*

 

„

3 .6V lithium 

industrial 

battery .

 

„

Replace without 

opening the 

enclosure .

 

„

12 - 24 VDC

 

„

Must be available when main is de-energized . 

 

„

Can be used with or without the network module* .

 

„

10/100 PoE

 

„

IEEE 802 .3af Type 1 Class III PoE topology .

*

Refer to network module instruction manual, available at www .panduit .com .

DC POWER INPUT

The 2 .0 AVT includes an optional DC Power Input . 

Recommended Wiring

DC Input and Connector Specifications

This connection features a pluggable screw-

terminal connector and is used for DC power 

input or connection to the network module 

(optional) .

 

„

Approved Power Source Type:  IEC Class I regulated power supply; 

                                                 12 - 24 VDC, 50 mA (minimum) output

 

„

Power Requirement:  35 mA max @ 12 VDC; 17 mA max @ 24 VDC

 

„

Connector / Wiring Requirements; 

Wire Range: (1 wire): AWG #24 - 12 [2 .5mm2] SOL / STR  

                    (2 wire): AWG #18 [1 .0mm2] SOL 

                                  AWG #18 [1 .5mm2] STR 

Wire strip length: 7 .0mm (min) / 8 .0mm (max) 

Screw Drive Size:  M3x0 .5 

Screw Torque Required:  5 .0 in-lb [0 .57 N-m] +/- 10%

Flashing - Test in Progress

Solid - Voltage may be Present

Equipment De-Energized, < 3V

Push Button to Begin Test

Hazardous Voltage Present

Line

   

Load

   

Other 

_________

Tester location:

   

# Flashes

Description

1
2

4

5, 6, 7 or 8

Check Battery
Voltage above Threshold

Installation Not Verified
See User Manual

3

Temperature Out of Range

See Diagnostic Code for Status: 

V

ERI

S

AFE 2.0

Absence of Voltage Tester

CAT IV (1000V), CAT IV (600V)

 

_________

 

 

Follow safety
procedures &

use required PPE

2.65

[67.3]

3.20

[81.3]

4

1

2

Network 

Module*

Isolation 

Module

1

2

Network 

Module*

Isolation 

Module

A1  

A2  B1 B2

AV

AUX

INDICA

TOR

DC P

ow

er I

nput

A

bsenc

e of

Voltage O

utputs

Pr

imar

y I

ndica

tor

M

odule I

nput

Sec

ond I

ndica

tor

M

odule I

nput

(optional)

Summary of Contents for VerySafe VS2-AVT Series

Page 1: ...Support Safety Information 2 Informations relatives la s curit 3 System Configuration 4 5 Components 4 Part Number Identification 4 Power for AVT Test 4 DC Power Input 4 Indicator Module 5 Absence of...

Page 2: ...standards The battery powered indicator module contains a lithium battery that is a fire explosion and severe burn hazard Do not crush recharge disassemble or heat above 85 C 185 F incinerate or expos...

Page 3: ...ient une pile au lithium qui pr sente un risque d incendie d explosion et de br lures graves Ne pas craser recharger d monter incin rer ou chauffer la pile plus de 85 C 185 F ni exposer son contenu l...

Page 4: ...h or without the network module 10 100 PoE IEEE 802 3af Type 1 Class III PoE topology Refer to network module instruction manual available at www panduit com DC POWER INPUT The 2 0 AVT includes an opt...

Page 5: ...ndicator module can be used in the AUX port however the battery will not have any impact on powering the AVT ABSENCE OF VOLTAGE OUTPUTS The AVT includes a set of redundant isolated transistor outputs...

Page 6: ...d 3 V See the Installation Considerations section for additional information Overvoltage Category III 1000 V IV 600 V Degree of Protection Indicator Module for flat surface mounting in a TYPE UL NEMA...

Page 7: ...fications UL 1436 Standard for outlet circuit testers and similar indicating devices CAN CSA C22 2 No 160 Voltage and polarity testers IEC UL CSA C22 2 NO 61010 1 IEC UL CSA C22 2 NO 61010 2 030 Safet...

Page 8: ...ation Flashes Description 1 2 4 5 6 7 or 8 Check Battery Voltage above Threshold Installation Not Verified See User Manual 3 Temperature Out of Range See Diagnostic Code for Status VERISAFE 2 0 Absenc...

Page 9: ...IGH LEG DELTA 3 WIRE NEUTRAL PE L3 L1 L2 L3 L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 L3 Neutral CORNER GROUNDED DELTA 3 WIRE PE L3 L1 L2 L2 L1 GND Isolation Module Enclo...

Page 10: ...L2 Ground Bond DC SYSTEM POSITIVE GROUND DC DC L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 Ground Bond DC SYSTEM 3 WIRE CENTER GROUND DC DC L2 L1 GND Isolation Module Enclo...

Page 11: ...e via a tap to the circuit conductor using connectors terminal strips or power distribution blocks etc which are rated for the application It is generally preferred to use connection methods that DO N...

Page 12: ...MODULE NETWORK MODULE DIN RAIL MOUNTING Snap the Isolation Module onto the DIN rail OR SURFACE MOUNTING Mount the isolation module to any surface using four 6 M3 5 pan head screws or another compatib...

Page 13: ...sure that contains the isolation mod ule the system cable must be installed in a conduit When installed in conduit the system cable should be regarded as a data cable and must not use the same conduit...

Page 14: ...mechanically connected to each other Instruction label Verify that a label is placed near each indicator module and marked to indicate where the AVT is installed Record changes to panel documentation...

Page 15: ...e the test has failed and flashes after a solid il lumination to indicate the reason for failure see Troubleshooting section for additional information VOLTAGE PRESENCE INDICATORS The red indicators i...

Page 16: ...s a stored energy source wait several minutes then re test to see if energy has dissipated 3 Temperature out of range Verify that the temperature of the isolation module is within the acceptable range...

Page 17: ...module to ensure the retention nut is tight and cap is firmly in place CLEANING INSTRUCTIONS The indicator module can be cleaned with a damp cloth or isopropyl alcohol based cleaner Do not use abrasi...

Page 18: ...CATOR MODULE For the battery free indicator module order Panduit SKU VS2 AVT GASKET for gasket replacement kit 1 Unplug the system cable and remove the panel nut 2 Squeeze the top and bottom of the ho...

Page 19: ...r 4 No Warranty for Third Party Products Panduit makes no representations and disclaims all warranties of any kind express or implied relative to any third party product or services including any thir...