Safety Information 

This manual contains information and warnings which must be followed to ensure safe operation of the AVT . If the AVT is not used as 

described in this manual, the safety features of the AVT might be impaired . 

Failure to comply with the warnings and information in this 

manual could result in product failure, electrical shock, severe injury or death.

Special Conditions 

of Use

Hazardous Locations

 

„

The equipment shall be installed in an enclosure that provides a degree of protection not less than 

IP 54 in accordance with IEC 60079-0 .

 

„

The enclosure must only be accessible with use of a tool .

 

WARNING:

 

„

Always de-energize power before accessing an electrical enclosure .

 

„

Always follow safety and lockout/tagout procedures when working on or near electrical systems and equipment .

 

„

Use of the AVT does not replace lockout/tagout procedures . The AVT is intended to be used in conjunction with lockout/tagout processes 

and only addresses the Absence of Voltage verification step .

 

„

Use proper personal protective equipment (PPE) when working around sources of hazardous electrical energy .

 

„

Do not use this product outside of the specified performance and environmental limits .

 

„

This product must be installed and commissioned by a qualified electrical worker familiar with local and national electrical codes .

 

„

The AVT will only test for absence of voltage at the point in the circuit where it is installed . If there are other sources of power in the equip-

ment, dangerous voltage may be present .

 

„

Lack of red voltage presence indicators alone does not verify the absence of voltage, the Absence of Voltage test must be initiated followed 

by the illumination only of the green indicator to verify the absence of voltage .

 

„

The AVT must be installed correctly and grounded as described in this Instruction Manual to provide proper indication of absence of voltage . 

Sensor leads must not be mechanically connected with each other for the device to verify connection to the circuit . Correct function of the 

device must be verified after installation, see Commissioning Checklist section, p . 14

 

„

Excess length from sensor leads should be trimmed .  Sensor leads should not be extended with a splice .  When using terminal or power 

distribution blocks, the total length of the sensor leads from the isolation module to the source conductors shall not exceed 10 feet (3 .0m) .

 

„

Sensor leads of the same label designation should be terminated on the same conductor (L1, L2, L3, GND) . Each conductor should have at 

least one sensor lead set, as shown on the schematic diagrams .

 

„

Always comply with local installation codes and standards .

 

„

The battery powered indicator module contains a lithium battery that is a fire, explosion and severe burn hazard . Do not crush, recharge, 

disassemble or heat above 85°C (185°F), incinerate, or expose contents to water .

 

„

The AVT will not work with a standard alkaline 1 .5 V AA battery .  Use only Panduit approved battery .

 

„

Use only 2 .0 AVT system components (system cable, isolation module, indicator module) .  Do not use a standard Ethernet cable .  Do not 

use 1 .0 AVT system components with 2 .0 AVT system components .

 

„

Battery, system cable, o-rings and gaskets can be replaced . No other part of the product is serviceable . Do not attempt to open the indicator 

module or isolation module for repair or modification . When servicing this product, only use specified replacement parts .

 

„

The section of the indicator module that is external to the electrical enclosure is approved for wash down when installed in an appropriate 

enclosure . Before a wash down operation, ensure the o-rings are in good condition, the faceplate is undamaged and fully secured to the unit 

and the cap is fully installed .

 

„

The AVT system cable must be separated from the sensor leads and other circuits in the electrical enclosure by a minimum of 0 .25 inches 

(6 mm) .

 

„

To prevent damage to the AVT in high-vibration installations, surface mount the isolation module using screws and secure the sensor lead 

wires and AVT system cable to prevent strain on the connection points .

 

„

Ensure all sensor leads are terminated properly and secured to the power conductor or other nearby rigid feature to prevent movement if 

the termination fails to remain intact .

 

„

The VeriSafe 2 .0 AVT is designed for use in 50 or 60Hz AC electrical systems and DC electrical systems . The AVT should not be installed on 

sections of a circuit where the AVT is exposed to high frequency energy such as variable frequency drives (VFD) or other circuit elements 

generating high frequency energy (waveforms exhibiting high Electro-Magnetic Interference (EMI)) . For more information on where to 

position the VeriSafe 2 .0 AVT in VFD applications, see the Technical Note available on Panduit .com .

Should a problem occur during installation, operation or maintenance of the VeriSafe 2 .0 AVT, contact Panduit technical support . Contact Panduit 

if you have any product problems related to the safety function of the product .  The product model number and serial number are printed on the 

isolation module and indicator module labels .

 VeriSafe 2 .0 AVT is a product containing electronic circuit boards in both the indicator and isolation modules . The indicator module contains a 

lithium battery . When decommissioning, remove the battery . Do not discard the battery in the trash; take it to an appropriate battery recycling 

facility . The indicator and isolation modules can be disposed of at an electronics recycling facility .

Summary of Contents for VerySafe VS2-AVT Series

Page 1: ...Support Safety Information 2 Informations relatives la s curit 3 System Configuration 4 5 Components 4 Part Number Identification 4 Power for AVT Test 4 DC Power Input 4 Indicator Module 5 Absence of...

Page 2: ...standards The battery powered indicator module contains a lithium battery that is a fire explosion and severe burn hazard Do not crush recharge disassemble or heat above 85 C 185 F incinerate or expos...

Page 3: ...ient une pile au lithium qui pr sente un risque d incendie d explosion et de br lures graves Ne pas craser recharger d monter incin rer ou chauffer la pile plus de 85 C 185 F ni exposer son contenu l...

Page 4: ...h or without the network module 10 100 PoE IEEE 802 3af Type 1 Class III PoE topology Refer to network module instruction manual available at www panduit com DC POWER INPUT The 2 0 AVT includes an opt...

Page 5: ...ndicator module can be used in the AUX port however the battery will not have any impact on powering the AVT ABSENCE OF VOLTAGE OUTPUTS The AVT includes a set of redundant isolated transistor outputs...

Page 6: ...d 3 V See the Installation Considerations section for additional information Overvoltage Category III 1000 V IV 600 V Degree of Protection Indicator Module for flat surface mounting in a TYPE UL NEMA...

Page 7: ...fications UL 1436 Standard for outlet circuit testers and similar indicating devices CAN CSA C22 2 No 160 Voltage and polarity testers IEC UL CSA C22 2 NO 61010 1 IEC UL CSA C22 2 NO 61010 2 030 Safet...

Page 8: ...ation Flashes Description 1 2 4 5 6 7 or 8 Check Battery Voltage above Threshold Installation Not Verified See User Manual 3 Temperature Out of Range See Diagnostic Code for Status VERISAFE 2 0 Absenc...

Page 9: ...IGH LEG DELTA 3 WIRE NEUTRAL PE L3 L1 L2 L3 L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 L3 Neutral CORNER GROUNDED DELTA 3 WIRE PE L3 L1 L2 L2 L1 GND Isolation Module Enclo...

Page 10: ...L2 Ground Bond DC SYSTEM POSITIVE GROUND DC DC L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 Ground Bond DC SYSTEM 3 WIRE CENTER GROUND DC DC L2 L1 GND Isolation Module Enclo...

Page 11: ...e via a tap to the circuit conductor using connectors terminal strips or power distribution blocks etc which are rated for the application It is generally preferred to use connection methods that DO N...

Page 12: ...MODULE NETWORK MODULE DIN RAIL MOUNTING Snap the Isolation Module onto the DIN rail OR SURFACE MOUNTING Mount the isolation module to any surface using four 6 M3 5 pan head screws or another compatib...

Page 13: ...sure that contains the isolation mod ule the system cable must be installed in a conduit When installed in conduit the system cable should be regarded as a data cable and must not use the same conduit...

Page 14: ...mechanically connected to each other Instruction label Verify that a label is placed near each indicator module and marked to indicate where the AVT is installed Record changes to panel documentation...

Page 15: ...e the test has failed and flashes after a solid il lumination to indicate the reason for failure see Troubleshooting section for additional information VOLTAGE PRESENCE INDICATORS The red indicators i...

Page 16: ...s a stored energy source wait several minutes then re test to see if energy has dissipated 3 Temperature out of range Verify that the temperature of the isolation module is within the acceptable range...