VeriSafe 2.0 AVT 

Operating Instructions

WARNING:

 

 

„

To avoid electric shock, always de-energize power before entering an electrical enclosure .

 

„

Always follow safety and lockout/tagout procedures when working on or near electrical systems and equipment .

 

„

Use proper personal protective equipment (PPE) when working around sources of hazardous electrical energy .

 

„

The product must be installed and commissioned by a qualified electrical worker familiar with local and national electrical 

codes .

 

„

The AVT will only test for absence of voltage at the point in the circuit where it is installed . If there are other sources of 

power in the equipment, dangerous voltage may be present .

 

„

Lack of red voltage presence indicators alone does not verify the absence of voltage, the absence of voltage test must be 

initiated followed by the illumination only of the green indicator to verify the absence of voltage .

The AVT should only be operated by individuals who have been trained on the operation of the tester and can demonstrate 

knowledge of the following criteria:

 

„

Familiar with requirements and information in the Instruction Manual and understand the function of the AVT, meaning of 

the indicators and markings, and limitations of the Voltage Presence Indicators .

 

„

Aware of where the AVT is installed in the electrical system and any additional electrical hazards that may be present in 

the system that are not detectable by the AVT .

 

„

Able to recognize electrical hazards and familiar with lockout/tagout procedures .

Indicator Module Faceplate

TEST BUTTON:

 Initiates test

ABSENCE OF VOLTAGE INDICATOR:

  Illuminates 

green

 when the absence of 

voltage is verified . 

CAUTION INDICATOR:

  Flashes 

yellow

 rapidly to indicate test in process, 

illuminates solid to indicate the test has failed and flashes after a solid il-

lumination to indicate the reason for failure, see Troubleshooting section 

for additional information . 

VOLTAGE PRESENCE INDICATORS:

  The 

red

 indicators illuminate when the 

presence of hazardous voltage is detected .  

Lack of red voltage pres-

ence indicators alone does not verify the absence of voltage.

 

VOLTAGE PRESENCE INDICATORS

A .  When voltage is detected in one or more phases, the 

appropriate voltage presence indicators will illuminate .

B .  Lack of red voltage presence indicators alone does not 

verify the absence of voltage .  To test for absence of 

voltage, push the test button . 

ABSENCE OF VOLTAGE TEST 

Each time the test button is engaged, the absence of voltage test sequence will be activated .  The test 

sequence includes running a self-check, using a known voltage source to test-the-tester to verify that 

the AVT is functioning, testing for AC and DC voltage phase-to-phase and phase-to-ground, and verify-

ing the sensor leads are in contact with circuit conductors .

1. 

De-energize the circuit according to company safety procedures .

2. 

Verify that lockout/tagout devices have been applied to all applicable energy sources and the volt-

age presence indicators are not illuminated .

3. 

Press the test button to initiate the absence of voltage test .

4. 

The caution indicator will begin to flash . This indicates that the test is in progress .

5. 

When the absence of voltage is verified, the absence of voltage indicator will illuminate .

6. 

If the absence of voltage is not verified, the caution indicator will illuminate for about five seconds 

followed by a series of flashes . The number of flashes will help diagnose why the test failed . Refer 

to the Troubleshooting section for additional information .

Voltage
Presence 
Indicators

Test Button

Absence

 of Voltage

 Indicator

Caution
Indicator

Voltage 
Presence 
Indicators

Test Button

Absence

of Voltage

Indicator

Caution
Indicator

Three-Phase

Single-Phase / DC

A

3

5

6

B

Summary of Contents for VerySafe VS2-AVT Series

Page 1: ...Support Safety Information 2 Informations relatives la s curit 3 System Configuration 4 5 Components 4 Part Number Identification 4 Power for AVT Test 4 DC Power Input 4 Indicator Module 5 Absence of...

Page 2: ...standards The battery powered indicator module contains a lithium battery that is a fire explosion and severe burn hazard Do not crush recharge disassemble or heat above 85 C 185 F incinerate or expos...

Page 3: ...ient une pile au lithium qui pr sente un risque d incendie d explosion et de br lures graves Ne pas craser recharger d monter incin rer ou chauffer la pile plus de 85 C 185 F ni exposer son contenu l...

Page 4: ...h or without the network module 10 100 PoE IEEE 802 3af Type 1 Class III PoE topology Refer to network module instruction manual available at www panduit com DC POWER INPUT The 2 0 AVT includes an opt...

Page 5: ...ndicator module can be used in the AUX port however the battery will not have any impact on powering the AVT ABSENCE OF VOLTAGE OUTPUTS The AVT includes a set of redundant isolated transistor outputs...

Page 6: ...d 3 V See the Installation Considerations section for additional information Overvoltage Category III 1000 V IV 600 V Degree of Protection Indicator Module for flat surface mounting in a TYPE UL NEMA...

Page 7: ...fications UL 1436 Standard for outlet circuit testers and similar indicating devices CAN CSA C22 2 No 160 Voltage and polarity testers IEC UL CSA C22 2 NO 61010 1 IEC UL CSA C22 2 NO 61010 2 030 Safet...

Page 8: ...ation Flashes Description 1 2 4 5 6 7 or 8 Check Battery Voltage above Threshold Installation Not Verified See User Manual 3 Temperature Out of Range See Diagnostic Code for Status VERISAFE 2 0 Absenc...

Page 9: ...IGH LEG DELTA 3 WIRE NEUTRAL PE L3 L1 L2 L3 L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 L3 Neutral CORNER GROUNDED DELTA 3 WIRE PE L3 L1 L2 L2 L1 GND Isolation Module Enclo...

Page 10: ...L2 Ground Bond DC SYSTEM POSITIVE GROUND DC DC L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 Ground Bond DC SYSTEM 3 WIRE CENTER GROUND DC DC L2 L1 GND Isolation Module Enclo...

Page 11: ...e via a tap to the circuit conductor using connectors terminal strips or power distribution blocks etc which are rated for the application It is generally preferred to use connection methods that DO N...

Page 12: ...MODULE NETWORK MODULE DIN RAIL MOUNTING Snap the Isolation Module onto the DIN rail OR SURFACE MOUNTING Mount the isolation module to any surface using four 6 M3 5 pan head screws or another compatib...

Page 13: ...sure that contains the isolation mod ule the system cable must be installed in a conduit When installed in conduit the system cable should be regarded as a data cable and must not use the same conduit...

Page 14: ...mechanically connected to each other Instruction label Verify that a label is placed near each indicator module and marked to indicate where the AVT is installed Record changes to panel documentation...

Page 15: ...e the test has failed and flashes after a solid il lumination to indicate the reason for failure see Troubleshooting section for additional information VOLTAGE PRESENCE INDICATORS The red indicators i...

Page 16: ...s a stored energy source wait several minutes then re test to see if energy has dissipated 3 Temperature out of range Verify that the temperature of the isolation module is within the acceptable range...

Page 17: ...module to ensure the retention nut is tight and cap is firmly in place CLEANING INSTRUCTIONS The indicator module can be cleaned with a damp cloth or isopropyl alcohol based cleaner Do not use abrasi...

Page 18: ...CATOR MODULE For the battery free indicator module order Panduit SKU VS2 AVT GASKET for gasket replacement kit 1 Unplug the system cable and remove the panel nut 2 Squeeze the top and bottom of the ho...

Page 19: ...r 4 No Warranty for Third Party Products Panduit makes no representations and disclaims all warranties of any kind express or implied relative to any third party product or services including any thir...

Reviews: