Commissioning Checklist: 

REPEAT THE COMMISSIONING CHECKLIST WHEN CHANGES TO THE ELECTRICAL SYSTEM ARE MADE.

 

‡

De-energize the circuit that is being monitored by the AVT .

 

‡

Visually inspect the AVT .

 

„

AVT system cable:

 Verify cable is locked into place on both the indicator module and isolation module .

 

„

DC power input:

  If an external DC power source is used to power the AVT, ensure the wiring from DC power source 

is connected and properly terminated into screw-terminal connector .  Ensure connector is fully seated .  Ensure the DC 

power source is fully functional .

 

„

Indicator module(s):

  Ensure o-ring and gaskets are in place .  Check that retaining nut is secure .  Verify battery is 

installed and battery cap is locked into place (if applicable) .

 

„

Isolation module:

 Ensure module is secured to subpanel or DIN rail .

 

„

Sensor leads:

 Gently pull on each sensor lead to ensure termination is secure .

 

„

Verify no wiring is exposed and all terminations are properly insulated .

 

„

Verify that leads are connected as described in the appropriate wiring diagram from the Schematic section, 

including verifying that each conductor has two lead wires of matching

 

label designation with no circuit elements 

between each pair .

 

„

Verify leads on each phase are not mechanically connected to each other .

 

„

Instruction label:

 Verify that a label is placed near each indicator module and marked to indicate where the AVT is 

installed .

 

‡

Record changes to panel documentation .

 

‡

Close panel and secure doors/covers .

 

‡

Press the test button to initiate the test . The yellow caution indicator should flash rapidly to indicate the test is in progress 

followed by the absence of voltage indicator illuminated green .

 

‡

Review the Operating Instructions section of this manual before proceeding .

WARNING:

 Always follow your company’s safety procedures when energizing equipment . To avoid electric shock, use proper 

personal protective equipment when working on or near electrical hazards .

 

‡

Energize the system being monitored by the AVT .

 

‡

Verify that the red voltage presence indicators are illuminated .

 

‡

Press the test button on the indicator module to initiate the absence of voltage test .

 

‡

Look for the yellow caution indicator to flash repeatedly before turning to a solid indication 

**You should not see the green indicator illuminate when power is energized**

 

‡

Repeat for each indicator module

 

‡

De-energize the circuit that is being monitored by the AVT .

 

‡

Verify that voltage presence indicators are not illuminated .

 

‡

Press the test button on the indicator module to begin the absence of voltage test .  Look for the yellow caution indicator 

to flash and then the green absence of voltage indicator should illuminate .

 

‡

Repeat for each indicator module .

Summary of Contents for VerySafe VS2-AVT Series

Page 1: ...Support Safety Information 2 Informations relatives la s curit 3 System Configuration 4 5 Components 4 Part Number Identification 4 Power for AVT Test 4 DC Power Input 4 Indicator Module 5 Absence of...

Page 2: ...standards The battery powered indicator module contains a lithium battery that is a fire explosion and severe burn hazard Do not crush recharge disassemble or heat above 85 C 185 F incinerate or expos...

Page 3: ...ient une pile au lithium qui pr sente un risque d incendie d explosion et de br lures graves Ne pas craser recharger d monter incin rer ou chauffer la pile plus de 85 C 185 F ni exposer son contenu l...

Page 4: ...h or without the network module 10 100 PoE IEEE 802 3af Type 1 Class III PoE topology Refer to network module instruction manual available at www panduit com DC POWER INPUT The 2 0 AVT includes an opt...

Page 5: ...ndicator module can be used in the AUX port however the battery will not have any impact on powering the AVT ABSENCE OF VOLTAGE OUTPUTS The AVT includes a set of redundant isolated transistor outputs...

Page 6: ...d 3 V See the Installation Considerations section for additional information Overvoltage Category III 1000 V IV 600 V Degree of Protection Indicator Module for flat surface mounting in a TYPE UL NEMA...

Page 7: ...fications UL 1436 Standard for outlet circuit testers and similar indicating devices CAN CSA C22 2 No 160 Voltage and polarity testers IEC UL CSA C22 2 NO 61010 1 IEC UL CSA C22 2 NO 61010 2 030 Safet...

Page 8: ...ation Flashes Description 1 2 4 5 6 7 or 8 Check Battery Voltage above Threshold Installation Not Verified See User Manual 3 Temperature Out of Range See Diagnostic Code for Status VERISAFE 2 0 Absenc...

Page 9: ...IGH LEG DELTA 3 WIRE NEUTRAL PE L3 L1 L2 L3 L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 L3 Neutral CORNER GROUNDED DELTA 3 WIRE PE L3 L1 L2 L2 L1 GND Isolation Module Enclo...

Page 10: ...L2 Ground Bond DC SYSTEM POSITIVE GROUND DC DC L2 L1 GND Isolation Module Enclosure External System Green Yellow L1 L2 Ground Bond DC SYSTEM 3 WIRE CENTER GROUND DC DC L2 L1 GND Isolation Module Enclo...

Page 11: ...e via a tap to the circuit conductor using connectors terminal strips or power distribution blocks etc which are rated for the application It is generally preferred to use connection methods that DO N...

Page 12: ...MODULE NETWORK MODULE DIN RAIL MOUNTING Snap the Isolation Module onto the DIN rail OR SURFACE MOUNTING Mount the isolation module to any surface using four 6 M3 5 pan head screws or another compatib...

Page 13: ...sure that contains the isolation mod ule the system cable must be installed in a conduit When installed in conduit the system cable should be regarded as a data cable and must not use the same conduit...

Page 14: ...mechanically connected to each other Instruction label Verify that a label is placed near each indicator module and marked to indicate where the AVT is installed Record changes to panel documentation...

Page 15: ...e the test has failed and flashes after a solid il lumination to indicate the reason for failure see Troubleshooting section for additional information VOLTAGE PRESENCE INDICATORS The red indicators i...

Page 16: ...s a stored energy source wait several minutes then re test to see if energy has dissipated 3 Temperature out of range Verify that the temperature of the isolation module is within the acceptable range...

Page 17: ...module to ensure the retention nut is tight and cap is firmly in place CLEANING INSTRUCTIONS The indicator module can be cleaned with a damp cloth or isopropyl alcohol based cleaner Do not use abrasi...

Page 18: ...CATOR MODULE For the battery free indicator module order Panduit SKU VS2 AVT GASKET for gasket replacement kit 1 Unplug the system cable and remove the panel nut 2 Squeeze the top and bottom of the ho...

Page 19: ...r 4 No Warranty for Third Party Products Panduit makes no representations and disclaims all warranties of any kind express or implied relative to any third party product or services including any thir...

Reviews: