- 18
2WAY SYSTEM
Outdoor Unit Repair Procedures
3
6. Evacuating System
6-2. Evacuating Refrigerant Tubing Between Indoor and Outdoor Units
Refer to the “Installation Instructions” that came with the outdoor unit.
Low-pressure outlet port
(for ø7.94mm-dia connector)
Liquid tube service port
(for ø7.94mm-dia connector)
Gas tube service port
(for ø7.94mm-dia connector)
18HP / 20HP type
Lo Hi
Manifold gauge
Vacuum pump
High-pressure outlet port
(for ø7.94mm-dia connector)
Fig. 7-c
High-pressure outlet port
(for ø7.94mm-dia connector)
Low-pressure outlet port
(for ø7.94mm-dia connector)
Gas tube service port
(for ø7.94mm-dia connector)
14HP / 16HP type
Lo Hi
Manifold gauge
Liquid tube service port
(for ø7.94mm-dia connector)
Vacuum pump
Fig. 7-b