2WAY SYSTEM
Control Functions
-
Outdoor Unit
1
- 42
1
Detail setting in EEPROM of outdoor unit
01 –4F: CCU parameters
DN
Item
Setting No
01
|
03
Invalid
-
04 Snow removal control
0(P), 1, 2, 3 (For detail refer to 5-8-2)
05 Silent mode
0(P), 1, 2,3,,, ,,,11 , 12 (For detail refer to 5-6)
06 Indoor fan mode in defrosting
0(P)=Stop 1=
LL
07 Invalid
-
08 Invalid
-
09
Indoor MOV pulse in heating Thermostat ON
(Fixed)
0(P)=Invalid, 5, 10, 15,,, ,,, 470, 480 pulse
0A
Indoor MOV pulse in heating Thermostat OFF
(Fixed)
0(P)=Invalid, 5, 10, 15,,, ,,, 470, 480 pulse
0B Stopped Indoor MOV pulse in heating mode (Fixed) 0(P)=Invalid, 5, 10, 15,,, ,,, 470, 480 pulse
0C Drain pump control
0, 1, 2,,, ,,, 6, 7(P) (For detail refer to 6-4)
0D Factory use
-
0E Cooling use only
0(P)=Invalid, 1=Cooling use only
0F Invalid
-
10 Invalid
-
11 Factory use
-
18 Factory use
-
19 Factory use
-
1A Upper current limitation setting for contact 1
-1=130, 0=Always stop, 40, 45, 50,,, 100(P),,, 125, 130
(For detail refer to 10)
1B Upper current limitation setting for contact 2
-1=130, 0=Always stop, 40, 45, 50,,, ,,,70(P),,, ,,, 125,
130 (For detail refer to 10)
1C Factory use
-
20 Factory use
-
21 Factory use
-
22 Factory use
-
23 E06 ignore function
-1(P) =Invalid, 0, 1,,, ,,,63
24 Dew condensation prevention
0(P)=Invalid, 1=valid (For detail refer to 7-6)
25 SH target shift value of K type indoor unit
0(P), 1, 2, 3, 4, 5
27 Auto change over function for 2way system
0(P)= =Invalid, 30, 40, 50, 60, 90, 120, 180, 240
(For detail refer to 13-2)
28
Stop time to perform 4way valve adjustment control
(Heating mode)
0(P)=60, 1=10, 2=20,,, ,,, 30=300 (For detail refer to 8)
29
Stop time to perform 4way valve adjustment control
(Cooling mode)
0(P)=60, 1=10, 2=20,,, ,,, 30=300 (For detail refer to 8)
2A Factory use
-
2B Drain pump’s operation time.
20, 30(P), 40, 50, 60 (For detail refer to 6-4)
2C Indoor fan control from CCU
-10, -9,,, 0(P),,, 20(For detail refer to 6-3-2)
2D
SC target value of indoor unit
0, 1, 2,,, 15(P),,, 24, 25
(P) : Factory preset mode