3
- 40
2WAY SYSTEM
Outdoor Unit Repair Procedures
3
9. Compressor
(7) Remove the bolts(3 locations), washers, and spacers.
* Use a crowbar to remove the cushioning rubbers just like inverter compressor removal procedure.
• Protect the sensors and surrounding plates, rubber, lead wires, clamps, and
other items.
Pay particular attention to protection of the oil equalizer tube connector parts,
and removal of the discharge sensor.
An O-ring is mounted inside the oil equalizer tube connector parts. It must be
protected and do not lose it.
CAUTION
(9) Disconnect the discharge tubing.
* Pull up the discharge tubing holding it with wet cloth.
(10) Disconnect the suction tubing.
* Protect the surrounding wiring, clamps, and rubber bands when brazing.
(11) Pull the compressor toward you.
(8) Remove the rubber band fixing the two tubes.
Cut the clamp and remove the rubber band.
First, disconnect the upper part of the
suction tubing (A) sideways. Then,
disconnect the suction tubing above the
compressor (B).
The disconnected tube is used later. So, do
not damage the tube.
A: Upper part of suction tubing
B: Suction tubing above the
compressor
SM830186-00̲2WAY ECO-i.indb 40
SM830186-00̲2WAY ECO-i.indb 40
2010/12/08 14:27:45
2010/12/08 14:27:45