2WAY SYSTEM
Control Functions-Outdoor Unit
1
4. Output of PCB
Item
Remarks
Indication on PCB
Electromagnetic valve
4 way valve
20S
Save valve
SAVE
Refrigerant control valve
RCV
Refrigerant balance valve
RBV
Oil recoverly valve
ORVR
By-pass valve for oil fl ushing
BPV
Refrigerant interception valve
O2
Motor Operated Valve
MOV for heat exchanger 1
MOV1
MOV for heat exchanger 2
MOV2
MOV for Sub cooler
MOV4
Crankcase heater
Crankcase heater for invertor
CH1
Crankcase heater for constant speed 1
CH2
Crankcase heater for constant speed 2
CH3
4-1. 4 way valve [20S]
- This valve turns OFF at cooling, and turns ON at heating operation.
- This valve turns OFF at defrosting.
* When the outdoor unit stops, the 4-way valve maintains the same state just before. However, when the system
stopped condition continues for 30 minutes, it is turned OFF.
4-2. SAVE valve [SAVE]
- This valve turns ON 5 seconds before the inverter compressor starts. After the inverter compressor starts, the
valve is ON for ten seconds. After that, it turns OFF.
- This valve turns ON for 30 seconds after the outdoor unit stops. After that, it turns OFF.
- This valve turns ON when high pressure sensor detects 3.4MPa to prevent abnormal pressure. This valve turns
OFF when the high pressure goes down below 3.3MPa.
Inverter compressor start
SAVE valve
5 sec
10 sec
Inverter compressor
- This valve might turn ON when the system capacity is excessive although the inverter compressor operates at
25Hz.
SAVE valve
3.3MPa
3.4MPa
High pressure