Control Functions-Outdoor Unit
1
11. Alarm Information
List of overcurrent
Inverter 6HP
Inverter 10HP
Secondary [ A ]
18.0
21.0
Primary [ A ]
18.0
23.0
11-2-2. Constant-speed compressor
An alarm occurs when overcurrent or lock current is detected.
List of overcurrent and lock currents
Constant-speed 5HP
Constant-speed 6HP
Overload current [ A ]
13.6
16.3
Lock current [ A ]
16.1
19.3
List of Alarms
Compressor No.
Compressor 2
Compressor 3
Detected current
Over current
Lock current
Over current
Lock current
Alarm display
H11
H12
H21
H22
11-2-3. CT circuit detection trouble
Alarm
Description
Compressor 1
(inverter compressor)
H03
Occurs when an open CT circuit is detected in the inverter compressor.
Compressor 2
H13
Occurs when an open CT circuit is detected in the constant speed
compressor.
Occurs when a current value of 1.5A or less is detected when the constant-
speed compressor is operating.
Compressor 3
H23
Occurs when an open CT circuit is detected in the constant speed
compressor.
Occurs when a current value of 1.5A or less is detected when the constant-
speed compressor is operating.
If the inverter compressor operating frequency is low, the current value is also low. Therefore this alarm is
detected only when the compressor is stopped.
The operating current of the constant-speed compressors is always higher than 1.5 A. Therefore, this alarm
occurs as the result of an open circuit or failure.
11-3. Pressure Sensor Failure
This system contains 2 types of pressure sensors: a high-pressure sensor and a low-pressure sensor.
11-3-1. High-pressure sensor failure
An alarm occurs when the high-pressure sensor becomes an electrical open-circuit or a short-circuit condi-
tions, and a broken wiring, short-circuit or poor connection to the PCB in the high-pressure sensor circuit for 30
seconds.
High-pressure sensor failure
Alarm display
F16
11-3-2. Low-pressure sensor failure
An alarm occurs when the low-pressure sensor becomes an electrical open-circuit or a short-circuit condi-
tions, and a broken wiring, short-circuit or poor connection to the PCB in the low-pressure sensor circuit for 30
seconds.
Low-pressure sensor failure
Alarm display
F17