2WAY SYSTEM
Control Functions
-
Outdoor Unit
1
- 10
1
3. Compressor Control
3-7-2. Overcurrent protection of compressor
Current limitation of compressor is shown in the table below. This limitation is to protect the compressor, so that
the current of the power cable connected with the compressor is limited.
* For the inverter compressor, this is the secondary current from HIC board.
Inverter 6 HP
Inverter 10 HP
Constant speed 5 HP
Constant speed 6HP
Limit current 2
18.0
21.0
13.6
15.7
Max. current 2 H
15.5
18.5
-
-
Max. current 2 L
15.0
18.0
-
-
Limit current 2
Max. current 2 H
Stop
If this current is detected at regular intervals, alarm appears.
Inverter compressor Hz goes down
Inverter compressor Hz can increase
Inverter compressor Hz cannot increase
Max. current 2 L
3-7-3. Primary current protection of HIC board
The fan motor current is included in primary current. PCB is protected from the power consumption increase of
fan motor when the heat exchanger is blocked by frost etc.
Inverter 6 HP
Inverter 10 HP
Limit current 1
18.0
23.0
Max. current 1 H
15.0
20.0
Max. current 1 L
14.5
19.5
Limit current 1
Max. current 1 H
Stop
If this current is detected at regular intervals, alarm appears.
Inverter compressor Hz goes down
Inverter compressor Hz can increase
Inverter compressor Hz cannot increase
Max. current 1 L
Reference
Invertor layout sketch
Diode Bridge
Power Source
IPM(FN)
Magnet SW
Noise Filter
L3
L1
L2
Noise Filter
IPM(CM)
Fan Motor
Compressor
W
U
V
W
U
V
Primary CT
Secondary CT
*When restarting after stopping by protection control, the compressor capacity will increase slowly.
H
L