2WAY SYSTEM
Control Functions-Outdoor Unit
1
10. Upper Current Limitation Mode
Serial-parallel I/O must be connected in order to perform upper current limitation mode. The below input is
received by serial-parallel I/O, and upper current limitation mode is performed.
The upper current limitation values can be set as needed with serial-prallel I/O.
Upper current
limitation setting
Control
Upper current limitation meaning
Contact 1 Contact 2
No control
Operates to maximum capacity.
Operates to XX% of the upper limit for the rated
current.
-
Operates to XX% of the upper limit for the rated
current..
-
Always in stop condition.
-
: Input present
: Input not present
* The rated current indicates the current value that is listed in the catalog or similar material.
* XX is able to set in EEPROM of main outdoor unit.
EEPROM setting in main outdoor unit
CODE: 1A, 1B
Demand setting
Control
Demand meaning
Contact 1 Contact 2
No limit
Operates to the
maximum capacity.
Demandcanbesetfrom40–200%at EEPROM1A.
Current is limited to the set values.
Demandcanbesetfrom40–200%at EEPROM1B.
Current is limited to the set values.
Remainsstopped.
-
* A1 has to be bigger than A2.