2WAY SYSTEM
Control Functions
-
Outdoor Unit
1
- 44
1
80 –FF: Outdoor unit parameters
DN
Item
Setting No
80 Invalid
-
81 Outdoor unit capacity
0, 22, 25, 28, 32, 36, 40, 45, 50, 56, 63, 71, 80, 90,
100, 112, 125, 140, 160, 180, 200, 224(8HP), 250,
280(10HP), 335(12HP), 355, 400(14HP), 450(16HP),
500(18HP), 560(20HP), 600, 630, 670, 710, 800, 840
82
|
86
Invalid
-
87 Max. inverter Hz of compressor
0, 5, 10, 15,,, ,,, 115, 120(P)
88 Min. inverter Hz of compressor
0, 5, 10, 15(P),,, ,,, 115, 120
89 Invalid
-
8E Invalid
-
8F High Static Pressure Mode
0(P)=Valid, 1=invalid, 2-6=No use
(For detail refer to 5-7)
90
|
96
Invalid
-
9A Invalid
-
9B Invalid
-
A0 Invalid
-
A1 Invalid
-
A2 Invalid
-
A3 The minimum operating time until defrosting
20, 21, 22, 35(P),,, ,,, 89, 90
(For detail refer to 9-4)
A4 Factory use
-
A5 Continuance time of fan step “0”
2, 3, 4, 5(P),,, ,,,8, 9 (For detail refer to 5-3)
A6 Factory use
-
A7 Capacity fi ne-tuning with MOV of indoor unit
0(P)=Valid, 1=invalid
A8 Invalid
-
A9
Indoor min. MOV pulse shift under SH control
(for indoor unit capacity 5.6kW or less)
-30, -29, -28,,, ,,, 49, 50
(For detail refer to 6-1-3)
AA
Indoor min. MOV pulse shift under SH control
(for indoor unit capacity 7.3kW)
-30, -29, -28,,, ,,, 49, 50
(For detail refer to 6-1-3)
AB
Indoor min. MOV pulse shift under SH control
(for indoor unit capacity over 10.6kW)
-30, -29, -28,,, ,,, 49, 50
(For detail refer to 6-1-3)
AD Max time of defrosting control
5, 6, 7,,, 12(P),,, 30 (For detail refer to 9-5)
B1 Pre-trip counts until “H06” alarm
3(P), 4, 5, 10, 20, 50
(For detail refer to 11-4-2)
B2 Invalid
-
B3 Pre-trip counts until “P03” alarm
5(P), 10, 20, 50 (For detail refer to 11-1-1)
B4 Pre-trip counts until “P17” alarm
5(P), 10, 20, 50 (For detail refer to 11-1-1)
B5 Pre-trip counts until “P18” alarm
5(P), 10, 20, 50 (For detail refer to 11-1-1)
B8 Factory use
-
B9 Factory use
-
BA Outdoor min. MOV1 pulse shift under SH control
-20, -19, -18,,, ,,, 29, 30 (For detail refer to 4-8-4)
BB Outdoor min. MOV2 pulse shift under SH control
-20, -19, -18,,, ,,, 29, 30 (For detail refer to 4-8-4)
BC Invalid
-
BD Invalid
-
BE Invalid
-