2WAY VRF SYSTEM
Control Functions
1
- 35
1
2
3
4
5
6
7
8
9
10. Upper Current Limitation Mode (Demand control)
3WAY SYSTEM
Control Functions
10. Upper Current Limitation Mode (Demand control)
Limit value
Limited ratio against standard value
Type of outdoor Unit
Even if the demand control is not performed, upper current limitation is restricted.
U-72ME2U94 / U-96ME2U94 / U-120ME2U94 / U-144ME2U94
(2) Upper Current Limitation Mode
72
96
120
144
140%
140%
140%
140%
Cooling mode
Heating mode
9.1 A
12.7 A
16.8 A
22.1 A
10.1 A
13.0 A
17.9 A
22.5 A
Limit value
Limited ratio against standard value
Type of outdoor Unit
U-72ME2U9 / U-96ME2U9 / U-120ME2U9 / U-144ME2U9
72
96
120
144
130%
130%
130%
130%
Cooling mode
Heating mode
18.3 A
25.2 A
32.5 A
44.4 A
19.8 A
26.9 A
35.6
A
45.0 A
(3) When Using Demand Terminal Block*
*Demand Terminal Block is the field supply parts.
Demand terminal block must be connected in order to perform the demand control.
(It is also possible to connect the optional Seri-Para I/O unit (optional CZ-CAPDC2) and setup the system.)
The current limitation values can be set by changing either contact.
* The rated current indicates the current value that is listed in the catalog or service manual.
During setting in DRM1 - DRM3,
[CZ-RTC5A] (demand-activated) displays on the
*
*
In respect of connection method for demand terminal block and Seri-Para I/O unit, refer to the installation
instructions supplied with the unit.
: Input present
: Input not present
Seri-Para I/O unit
Demand terminal block
COM short circuit
Non
DRM3
DRM2
DRM1
Contact 1 Contact 2
No control (Operates to maximum capacity.)
Operates to 100% of the upper limit for the rated current
Operates to 70% of the upper limit for the rated current
Control
Forced thermostat OFF setting
[CZ-RTC4]
remote controller of the indoor unit.
EEPROM setting in main outdoor unit
CODE: 1E
Setting No.
0
No display
1
When demand control active, “demand - actived” displayed (factory preset mode).
2
When forced thermostat OFF with demand control active, “demand - actived” displayed.
It is able to display the present condition on the remote controller.