2WAY VRF SYSTEM
Outdoor Unit Repair Procedures
2
- 20
1
2
3
4
5
6
7
8
9
7. Charging Compressor Oil
2WAY VRF SYSTEM
Outdoor Unit Repair Procedures
7. Charging Compressor Oil
7-2. If Outdoor Unit Has Not Been Charged with Refrigerant
When a compressor has been replaced or in any other case where the outdoor unit has not been charged with
refrigerant, first charge with refrigerant then follow the instructions in “7-1. If Refrigerant Has Already Been
Charged to Outdoor Unit” and charge with oil.
Or, alternatively, follow the procedure below.
(1) Connect a tube to the oil outlet port on the outdoor unit to be charged with oil. Insert the other end of the tube
into the oil container.
(2) Follow the instructions in “6. Evacuating System,” and apply vacuum to the outdoor unit to be charged with oil.
When this is done, oil is charged into the outdoor unit through the oil outlet port.
(3) When the unit has been charged with the designated amount of oil, stop the vacuum pump.
The oil absorbs moisture readily. This work must be completed quickly.
CAUTION
Lo
Hi
Manifold
gauge
Vacuum pump
High-pressure outlet port
(for ø5/16” (ø7.94mm)-
dia connector)
Type: 72, 96
Low-pressure outlet port
(for ø5/16” (ø7.94mm)-
dia connector)
Liquid tube service port
(for ø5/16” (ø7.94mm)-
dia connector)
Gas tube service port
(for ø5/16” (ø7.94mm)-
dia connector)
Oil
Balance tube service port
(for ø5/16” (ø7.94mm)-
dia connector)
Fig. 13
SM830237-07_北米向け2WAY_VRF.indb 20
18/06/18 18:48:15