2WAY VRF SYSTEM
Remote Controller Functions
4
- 20
1
2
3
4
5
6
7
8
9
2. Detailed Settings Function
Auto External Static Pressure Setting Operation
6. Keep pressing the
,
and
buttons simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the
LCD display.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Page [
] Confirm
20:30 (THU)
7. Press the
or
button to see each
menu. If you wish to see the next screen instantly,
press the
or
button.
Select “4. Test run” on the LCD display and press
the
button.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Page [
] Confirm
20:30 (THU)
The “Test run” screen appears on the LCD display.
[
] Confirm
Test run
Change
20:30 (THU)
Test run
OFF
Change the display from OFF to ON by pressing
the
or
button. Then press the
button.
[
] Confirm
Test run
Change
20:30 (THU)
Test run
ON
The “Maintenance func” screen appears on the
LCD display.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Page [
] Confirm
20:30 (THU)
8. Press the
button. “TEST” will be displayed
on the LCD display.
TEST
START
[ ]
20:30 (THU)
9. Press the
button. Test run will be started.
Test run setting mode screen appears on the LCD
display.
TEST
FAN SPEED
FLAP
20:30 (THU)
COOL
MODE
10. Set the operation mode to “
” and fan speed
mode to “
” by pressing the
or
button or
or
button. Then press the
button.
TEST
MODE
FAN SPEED
FLAP
FAN
20:30 (THU)
The fan motor will be activated, the auto external
static pressure setting operation and setting-check
operation will be performed for about 3 to 30 minutes.
The fan speed will change automatically while these
operations are in progress. When these operations
completed, “TEST” will be disappeared from the LCD
display.
MODE
FAN SPEED
FLAP
FAN
20:30 (THU)
NOTE:
The auto external static pressure setting operation and
setting-check operation will not be performed unless
“
(MODE FAN)” and “
(FAN SPEED)” have
been selected.
11. Press the
button.
The LCD display will be returned to the initial
screen.
START
[ ]
20:30 (THU)
NOTE:
Failure to set this parameter may result in
decreased airflow and condensation.