2WAY VRF SYSTEM
Outdoor Unit Maintenance Remote Controller
3
- 6
1
2
3
4
5
6
7
8
9
3. Ordinary Display Controls and Functions
n
Display (functions)
•
Use the temperature setting
and
buttons to change the item code.
À
Item code
Á
Item
Remarks
Outdoor unit alarm
Alarm code display
No. of connected indoor units
Quantity
Unit Nos. of connected indoor unit
7-segment display
Operating status of indoor unit
7-segment display
Thermostat ON status of indoor unit
7-segment display
No. of connected outdoor units
1 – 3
Unit Nos. of connected outdoor units
7-segment display
Operating status of outdoor unit compressor
7-segment display
1st compressor operating time
0 – 99999999 hours
2nd compressor operating time
0 – 99999999 hours
1st compressor oil level
0 = Empty 1 = Insufficient 2 = Sufficient
2nd compressor oil level
0 = Empty 1 = Insufficient 2 = Sufficient
Outdoor unit power ON time
0 – 99999999 hours
1st compressor operation count
0 – 65535 times
2nd compressor operation count
0 – 65535 times
Alarm history 1 (most recent)
Display only. Alarm code and unit No. of unit
where alarm occurred are displayed alternately.
0 = CCU
1 – 3 = Outdoor unit
Alarm history 2
Alarm history 3
Alarm history 4
Alarm history 5
Alarm history 6
Alarm history 7
Alarm history 8 (oldest)
Firmware version
Display the version No. × 100.
Program version
Display the version No. × 100.
À
and
Á
correspond to Fig. 1 on the next page.