2WAY VRF SYSTEM
Remote Controller Functions
4
- 7
1
2
3
4
5
6
7
8
9
1. Simple Settings Function
When the operating mode at the priority remote controller is changed, the operating modes of other remote
controllers change as shown below.
Mode change at priority remote controller Operating modes at other remote controllers
Current mode
New mode
Current mode
New mode
Cooling or dry
Heating
Cooling or dry
Heating
Fan
Fan (not changed)
Heating
Cooling
Heating
Cooling
Fan
Fan (not changed)
Cooling
Dry
Cooling
Cooling (not changed)
Dry
Dry (not changed)
Heating
Dry
Heating
Cooling
Fan
Fan (not changed)
Cooling or dry
Fan
Cooling
Cooling (not changed)
Dry
Dry (not changed)
Fan
Fan (not changed)
Heating
Fan
Heating
Heating (not changed)
Fan
Fan (not changed)
Item code
Item
Description
05
Fan speed setting when
heating thermostat is OFF
Changes the fan speed setting when the heating thermostat is OFF.
06
Heating intake temperature
shift
Shifts the intake temperature during heating.
Can be set when the body thermostat is used.
07
Electric heater installation
Set when cost distribution is performed using an AMY central control system
or similar system, and when an optional electric heater is installed.
(This is unrelated to control of the electric heater.)
08
Humidifying when heater
thermostat is OFF
Normally humidifying does not occur when the thermostat is OFF during
heating operation. However, this setting can be changed in order to increase
the amount of humidifying.
Caution: In order to avoid water leakage and damage to the fan, do not use
this setting unless a vaporizing humidifier is used.
0D
Permit/prohibit automatic
heating/cooling
This setting can be used to prevent the automatic heating/cooling display on
the remote control if the unit configuration permits automatic heating/cooling
operation.
0F
Cooling-only
This setting allows a heat pump indoor unit to be operated as a cooling-only
unit.