2WAY VRF SYSTEM
Trouble Diagnosis
3. 2WAY Alarm Codes
L10 Alarm
Alarm code
L10
Alarm meaning
Capacity setting of outdoor unit is not correct.
Alarm conditions
The outdoor unit capacity has not been set, or the setting is not allowed by the system.
Probable cause
This alarm occurs because the capacity has not been set.
Check
Connect the outdoor unit maintenance remote controller. On the outdoor unit EEPROM detailed setting
mode screen, check the value for the outdoor unit capacity (item code 81).
Check that it is not set to “0” or to a capacity that is not allowed.
U-72/96/120/144ME2U9
Number of compressor
JP7 in CTL board
item code: 81
Type of outdoor unit
1
open
210, 280
72, 96
2
short
355, 420
120, 144
U-72/96/120/144ME2U94
Number of compressor
HIC1
HIC2
item code: 81
Type of outdoor unit
1
7 pieces electric wire
—
210, 280
72, 96
2
8 pieces electric wire 7 pieces electric wire
355, 420
120, 140
Correction
If item code 81 is incorrect, use the outdoor unit maintenance remote controller and set it correctly.
* After changing the setting, be sure to reset both the indoor and outdoor power.
Example
—
Notes
The outdoor unit maintenance remote controller is required in order to set the capacity in the outdoor unit
EEPROM.