2WAY VRF SYSTEM
Remote Controller Functions
4
- 14
1
2
3
4
5
6
7
8
9
2. Detailed Settings Function
Item code
Item
Description
10
Unit type
Set when the indoor unit EEPROM memory is replaced during servicing.
11
Indoor unit capacity
12
System (outdoor unit)
address
These are not set at the time of shipping from the factory.
These must be set after installation if auto address setting is not performed.
13
Indoor unit address
14
Group address
17
Cooling intake temperature
shift
Shifts the intake temperature during cooling and dry operation.
(Enabled only when the body thermostat is used.)
Increase this value when it is difficult to turn the thermostat ON.
18
Automatic stop time after
operation start
The time at which an indoor unit is automatically stopped after operation starts
can be set in increments of 5 minutes.
1E
Temperature shift for
cooling/heating change in
“auto heat/cool” mode
“Auto heat/cool” selects the operating mode automatically based on the
difference between the room temperature and the temperature set on the
remote controller. This setting establishes a shift temperature for the heating/
cooling temperature setting relative to the remote controller temperature
setting.
Cooling temperature setting
Remote controller temperature setting
Heating temperature setting
Shift temperature
(+)
Shift temperature
(–)