19.2 Heating Capacity Table
Water Out
25ºC
35ºC
Outdoor Air
Capacity(W)
Input Power(W)
Current(A)
Capacity(W)
Input Power(W)
Current(A)
-20
16000
7400
11.1
16000
8400
12.6
-15
15300
6100
9.1
16000
6910
10.3
-7
19000
6600
9.9
16000
6700
10.0
2
20600
5350
8.0
16000
5160
7.7
7
16000
2800
4.2
16000
3540
5.3
25
16000
1550
2.3
16000
2300
3.4
Water Out
45ºC
55ºC
60ºC
Outdoor Air
Capacity(W)
Input
Power(W)
Current(A)
Capacity(W)
Input
Power(W)
Current(A)
Capacity(W)
Input
Power(W)
Current(A)
-20
16000
10000
14.9
14000
10300
15.4
-
-
-
*
-15
16000
8440
12.6
16000
9970
14.9
14000
10600
15.8
-7
16000
7850
11.7
16000
9330
13.9
15000
9700
14.5
2
16000
6400
9.6
16000
7720
11.5
16000
9200
13.7
7
16000
4550
6.8
16000
5600
8.4
15600
6500
9.7
25
16000
3200
4.8
16000
4000
6.0
15500
4500
6.7
Note:
* Between outdoor ambient -15°C and -20°C, the water outlet temperature gradually decreases from 60°C to 55°C.
* Only when ΔT is set to 15°C, the set temperature above 60°C will take effect.
19.3 Cooling Capacity Table
OD
Water Out 7ºC
Water Out 14ºC
Water Out 18ºC
Capacity(W)
Input
Power(W)
Current(A) Capacity(W)
Input
Power(W)
Current(A) Capacity(W)
Input
Power(W)
Current(A)
16
15000
3150
4.7
19000
3350
5.0
19000
3000
4.5
25
15000
4000
6.0
18000
4000
6.0
18000
3500
5.2
35
14500
5110
7.6
14500
4200
6.3
16000
4270
6.4
43
9500
4400
6.6
11500
4400
6.6
12500
4300
6.4