137
16.1.4 Specifications
16.1.4.1 Specifications of Fresh Water was Heat Transfer Medium in Brazed Heat
Exchanger
Parameter
Quality Limits for Tap Water on the Secondary Side
Temperature
Below 60°C
pH
7 to 9
Alkalinity
60mg/I <HCO
3
<300mg/I
Conductivity
< 500μS/cm
Hardness
[Ca
+
, Mg
+
] / [HCO
3
-
] > 5
Chloride
< 200mg/l at 60°C
Sulphate
[SO
4
2-
] > 100mg/I and [HCO
3
-
] / [SO
4
2-
] > 1
Nitrate
NO
3
< 100mg/I
Chlorine
< 0.5mg/l
16.1.4.2 External
Filter
Solids in the water must be filtered.
Minimum filter mesh size required for the field supply external filter in the water inlet is 20 mesh.