88
Buffer Tank connection select "NO" &
o
One zone system is select
This zone room temperature control by either one of the 4 room sensor (Room Th, Int/Ext Room
Thermostat, Water temp.)
Target Zone Water Temperature calculate base on selected temperature control type (Compensation or
Direct) and selected room sensor.
Target Water Temperature will set same as Target Zone Water Temperature
Target Water Temperature is a temperature for heat pump to operate refer to indoor water outlet sensor.
Heat pump and water pump OFF when ROOM Thermo OFF (Zone thermo OFF by Room Th or Room
Thermostat).
* There will be no zone sensor connected to zone 1 (No zone sensor error), mixing valve and zone pump will not
operate.
o
2 zone system select
Each zone room temperature is control by each sensor which select from either one of the 4 room sensor
Target Zone 1 & 2 Water Temperature is calculated based on selected temperature control type
(Compensation or Direct) and selected room sensor.
* Zone Mixing Valve & Zone pump will operate to achieve Target Zone Water Temperature which refer to
zone sensor.
* Zone Sensor will detect if zone sensor is open or short.
Target Water Temperature will set same as the active & higher zone water temperature setting. (When
cooling mode, lower zone water temp setting)
Target Water Temperature is the temperature for heat pump to operate refer to indoor water outlet
sensor.
Heat pump and water pump OFF when ROOM Thermo OFF (Both Zone thermo OFF by Room Th or
Room Thermostat).
Buffer Tank Connection select "YES" &
o
1 zone system or 2 zone system select
Each zone control by each sensor which select from either one of the 4 room sensor
Target Zone 1 & 2 Water Temperature calculate base on selected temperature control type
(Compensation or Direct) and selected room sensor. Each zone have their own Target Zone Water
Temperature.
* Zone Mixing Valve & Zone pump will operate to achieve each Target Zone Water Temperature which
refer to zone sensor
* Zone Sensor will detect if zone sensor is open or short.
Target Buffer Tank Temperature will be set as active & higher zone water temperature s Buffer
Delta T. (Heating) Target Buffer Tank Temperature will be set as active & lower zone water temperature
setting (Cooling).
Target Water Temperature will set as Target Buffer Tank Tempe [2°C] (Heating) Target Water
Temperature will set as Lower or Active Target Zone Water Temp. + [-3°C] (Cooling)
Target Water Temperature is a temperature for heat pump to operate refer to indoor water outlet sensor.
Heat pump and water pump OFF when ROOM thermo OFF
Heat mode: ROOM thermo OFF (Buffer Tank Temperature
>
Target Buffer Tank + [0°C]
Cool mode: ROOM Thermo OFF (Both Zone thermo OFF by Room Th or Room Thermostat)
13.1.7 Auto Mode Operation
Outdoor Ambient
Cool To Heat
Setting Temp.
COOL
MODE
HEAT
MODE
Heat To Cool
Setting Temp.