123
14.1.5 High Pressure Sensor Control
Purpose:
- To protect the system operation.
Detection period:
- After compressor on for 1 minute.
Detection conditions:
- When abnormal high voltage detection, 5 V or when open circuit detection 0V for 5 seconds continuously.
After detection:
- When abnormality is detected 4 times within 120 minutes, unit stop operation.
- OFF/ON control panel LED will blink (H64 error occurs).
14.1.6 Outside Temperature Current Control
23°C
21°C
14°C
12°C
-28°C
-30°C
Compressor operate
with limited operation
Outdoor temperature
Max.
current
value is
regulated
14.1.7 Crank Case Heater Control
Purpose:
- For compressor protection during low outdoor ambient operation (during heating low temperature operation).
Control content:
a. Trigger heater START condition
o
When the outdoor air temperature is below than 4/5°C, and discharge temperature is 9/11°C or below.
b. Resetting heater STOP condition
1.
When the outdoor air temperature exceeds entry condition (6/7°C)
2. When the discharge temperature exceeds entry condition (13/16°C)
WH
‐
MXC16J9E8
Start condition
Outdoor air temperature
5°C
Discharge temperature
11°C
Stop condition
Outdoor air temperature
7°C
Discharge temperature
16°C