58
12.1.10 Maintenance
In order to ensure optimal performance of the unit, seasonal inspections on the unit, functional check of RCCB,
field wiring and piping have to be carried out at regular intervals. This maintenance should be carried out by
authorized dealer.
12.1.10.1 Maintenance for Magnetic Water Filter Set
⑬
1. Remove the Cover
⑰
by loosening the mounting screws to access to the Magnetic Water Filter Set
⑬
.
2. Turn OFF power supply.
3. Set the two valves for the Magnetic Water Filter Set
⑬
to “CLOSE”.
4. Take off the clip, then gently pull out the mesh. Beware of small amount water drain out from it.
5. Clean the mesh with warm water to remove all the stain. Use soft brush if necessary.
6. Reinstall the mesh to the Magnetic Water Filter Set
⑬
and set back the clip on it.
7. Set the two valves for the Magnetic Water Filter Set
⑬
to “OPEN”.
8. Turn ON power supply.
9. After cleaning, reinstall the Cover
⑰
by tightening the mounting screws properly.
WARNING
Do not add or replace other than R32 type. It may cause product damage, burst, injury and etc. Use compatible R32 tools for
refrigerant piping work and refrigerant charging during installation or servicing.
Mounting
screws
Cover
17