79
Auto
30. Outdoor temp. for (Heat to Cool)
Initial setting: 15°C
15°C
Heat
Cool
Outdoor temp. rising
Set outdoor temp that switches from heating to cooling by Auto setting.
Setting range is 5°C ~ 25°C
Timing of judgement is every 1 hour
31. Outdoor temp. for (Cool to Heat)
Initial setting: 10°C
10°C
Heat
Cool
Outdoor temp. dropping
Set outdoor temp that switches from Cooling to Heating by Auto setting.
Setting range is 5°C ~ 25°C
Timing of judgement is every 1 hour
Tank
32. Floor operation time (max.)
Initial setting: 8h
Heat
Tank
30min ~ 10h
Set max operating hours of heating.
When max operation time is shortened, it can boil the tank more frequently.
It is a function for H Tank operation.
33. Tank heat up time (max.)
Initial setting: 60min
Heat
Tank
5min ~ 4h
Set max boiling hours of tank.
When max boiling hours are shortened, it immediately returns to Heating operation, but it may
not fully boil the tank.
34. Tank re-heat temp.
Initial setting: -8°C
-12°C ~ -2°C
Set temp to perform reboil of tank water.
Setting range is -12°C ~ -2°C
35. Sterilization
Initial setting: 65°C 10min
②
① ③
Set timer to perform sterilization.
Set operating day & time. (Weekly timer format)
Sterilization temp (55~75°C
If use back-up heater, it is 65°C)
Operation time (Time to run sterilization when it reached setting temp 5min ~ 60min)
User shall set whether to use or not to use sterilization mode.
①
②
③