13.24 Two Ways Valve Control
Functionality of 2 ways valve:
Use to allow hot water to floor heating panel or block cold water to floor heating panel.
Control contents:
1 When indoor running in heat mode, OPEN the 2 ways valve.
2 When indoor running in cool mode, CLOSE the 2 ways valve.
3 Stop condition:
a.
During stop mode, fix 2 ways valve in close condition.
L
N2
Indoor Unit
N1
Spring Return 2 point
SPDT 3 wire
M
L
N1
N2
COM
Open
Close
M
L
NC
N1
N2
M
L
NO
N1
N2
AC230V
* During pump down mode, fix 2 ways valve in close condition.
* During force mode, open 2 ways valve.
* Recommended Parts : SFA 21/18 (Siemens)
13.25 External OFF/ON Control
Communication circuit between indoor unit and external controller is as per below.
External
Controller
Panasonic
PCB
CN-THERMO
5V
12V
1
2
mico
Maximum length of communication cable is 50 meter.
Control content:
External Control Switch
Control Panel OFF/ON
Control Panel Power LED
System Status
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF