181
17.5.37 Indoor Water Outlet Temperature Sensor 2 Abnormality (F30)
Malfunction Decision Conditions:
During startup and operation of cooling and heating, the temperatures detected by the indoor water outlet
temperature sensor 2 are used to determine sensor error.
Malfunction Caused:
1 Faulty connector connection.
2 Faulty sensor.
3 Faulty indoor unit PCB.
Abnormality Judgment:
Continue for 5 seconds.
Troubleshooting:
For safety reason and to prevent component breakdown,
always switch off the power before remove and connect the component.
Indoor Refrigerant Liquid / Water Inlet / Water
Outlet Sensor Characteristic
-10
0
10
20
30
40
50
50
60
70
80
90
100
110
120
40
30
10
20
0
Temperature (°C)
R
esis
tance
(K
)
No
No
Yes
Yes
Check the CN-TH3 connector connnection:
- Turn OFF the power
- Check the connector connection
- Connector poor contact
- Correct the connection
- Defect in indoor water outlet
temperature sensor
- Replace the indoor water
outlet temperature sensor
- Defect in indoor unit PCB
- Replace the indoor unit PCB
Check the indoor water outlet temperature sensor:
- Plug out connector from the indoor unit PCB
- Measure the resistance of the indoor water outlet
temperature sensor
Is the CN-TH3 connector
connection normal?
Is the measured resistance of the
indoor water outlet temperature
sensor matches the value specified
in its characteristic chart?
Caution