<Procedure of CZ-RTC5B>
1 Keep pressing the
,
and
buttons simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the
LCD display.
2 Press the
or
button to see each
menu.
If you wish to see the next screen instantly, press
the
or
button.
the
button.
Change the display from OFF to ON by pressing
the
or
button. Then press the
button.
Fig. 7-8
3 Press the
button. “TEST” will be displayed
on the LCD display.
4 Press the
button. Test run will be started.
Test run setting mode screen appears on the LCD
display.
SM830255-00_Single_欧州4方向 TD&SM.indb 22
16/09/21 13:54:54
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4. Test run
Sel.
Page [
] Confirm
20:30 (THU)
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4. Test run
Sel.
Page [
] Confirm
20:30 (THU)
[
] Confirm
Test run
Change
20:30 (THU)
Test run
ON
20:30 (THU)
START
[ ]
TEST
START
[ ]
20:30 (THU)
TEST
FAN SPEED
FLAP
TEST
20:30 (THU)
COOL
MODE
Select “4. Test run” on the LCD display and press
7-18
SM830277-00_大洋州向け R32シングル_TD&SM.indb 18
19/02/28 13:40:12
Summary of Contents for S-160PE1R5B
Page 12: ...MEMO Xi SM830277 00_ R32 _TD SM indb 12 19 02 26 9 34 28...
Page 136: ...MEMO 2 16 SM830277 00_ R32 _TD SM indb 16 19 02 28 13 25 27...
Page 164: ...MEMO 4 22 SM830277 00_ R32 _TD SM indb 22 19 02 21 11 54 26...
Page 202: ...MEMO 5 38 SM830277 00_ R32 _TD SM indb 38 19 02 28 13 37 39...
Page 274: ...201903 SM830277 00_ R32 _TD SM indb 1 19 02 12 9 03 53...