Suspending the Indoor Unit
Depending on the ceiling type:
1. Check the suspension bolt pitch.
2. Ensure that the ceiling is strong enough to support the weight of the unit.
3. To prevent the unit from dropping, firmly fasten the suspension bolts as shown in the figure below.
L*
20 ~ 50
Hole-in-anchor
Hole-in-plug
Insert
Unit: mm
Concrete
Suspension bolt
(field supply)
Hexagonal nut (field supply)
Special washer (field supply)
Special washer (field supply)
Hexagonal nut (field supply)
Suspension bolt (field supply)
Hexagonal nut (field supply)
Special washer (supplied)
Special washer (supplied)
Suspension lug
Hexagonal nut (field supply)
* Choose “L” dimension according to the status of the ceiling.
Fig. 1-11-2-2-1
Fig. 1-11-2-2-2
NOTE
Suspension bolt
(field supply)
M10 or 3/8”
WARNING
It is important that you use extreme care in supporting the indoor unit
inside the ceiling.
Ensure that the ceiling is strong enough to support the weight of the unit.
Before suspending the unit, test the strength of each attached
suspension bolt.
(1) When placing the unit inside the ceiling, determine the pitch of the suspension bolts referring to the dimensional data given previously.
Tubing must be laid and connected inside the ceiling when suspending the unit.
If the ceiling is already constructed, lay the tubing into position for connection to the unit before placing the unit inside the ceiling.
(2) Screw in the suspension bolts allowing them to protrude from the ceiling as shown in Fig. 1-11-2-2-1. (Cut the ceiling material, if necessary.)
(3)
Suspend and fix the indoor unit using the 2 hexagonal nuts (field supply) and special washers (supplied with the unit) as shown in Fig. 1-11-2-2-2.
CAUTION
•
The top of the unit must be installed horizontally.
Horizontal
level
•
Check the unit is placed horizontally.
Make sure the unit is installed level using a level or a
vinyl hose filled with water.
In using a vinyl hose instead of a level, adjust the top surface of the unit to the surface of the water
at both ends of the vinyl hose and
make horizontal adjustment on all 4 corners of the unit.
If the air discharge side of the unit is installed downward, splashing water or water leak may occur.
Also, the dust may accumulate inside the drain pan caused by draining residual water.
• When lifting the unit, do not attempt to hold the electrical component box in hand.
Carpenter’s level
Vinyl hose filled with water
Electrical component box
Installing the Refrigerant Tubing
The size of the refrigerant tubing is as shown in the table below.
Table 1-11-2-2-1
Type
180
200 / 224
Gas tube
ø19.05 (~ 50 m)
ø25.4 (Over 50 ~ 75 m)
(Brazing connection)
ø19.05 (~ 30 m)
ø25.4 (Over 30 ~ 60 m)
(Brazing connection)
Liquid tube
ø9.52 (Flare connection)
Tightening torque (approximate)
: 34 ~ 42 N
•
m
Thickness of connecting tube
: 0.8 mm
ø12.7 (Flare connection)
Tightening torque (approximate)
: 49 ~ 55 N
•
m
Thickness of connecting tube
: 0.8 mm
NOTE
To fasten the flare nuts, apply specified torque.
SM830277-00_大洋州向け R32シングル_TD&SM.indb 4
2019/02/27 11:51:06
Summary of Contents for S-160PE1R5B
Page 12: ...MEMO Xi SM830277 00_ R32 _TD SM indb 12 19 02 26 9 34 28...
Page 136: ...MEMO 2 16 SM830277 00_ R32 _TD SM indb 16 19 02 28 13 25 27...
Page 164: ...MEMO 4 22 SM830277 00_ R32 _TD SM indb 22 19 02 21 11 54 26...
Page 202: ...MEMO 5 38 SM830277 00_ R32 _TD SM indb 38 19 02 28 13 37 39...
Page 274: ...201903 SM830277 00_ R32 _TD SM indb 1 19 02 12 9 03 53...