1-11-2-2-8
1
1
1-1. How to Set on PC Board
1. Turn off the power breaker to halt the supply of electricity to the PC board.
2. Open the lid of the electrical component box and confirm the location where the Select switch on the indoor unit control PCB is
placed. (Fig. 1-11-2-2-3)
3. Set the On/Off switches in the Off position which are now set in the On position.
Select the positions of the Select SW001 switches respectively to make the desired external static pressure settings referring to
the Table 1-11-2-2-2.
Table 1-11-2-2-2 External static pressure SW setting
External static pressure at the
time of rated airflow volume
SW001
180
200
224
TP6
TP3
TP1
150Pa
180Pa
200Pa
ON
1
2
3
100Pa
120Pa
130Pa
1
ON
2
3
60Pa
75Pa
75Pa
1
2
ON
3
Table 1-11-2-2-3 Setting the external static pressure
Indoor unit
Item code
180
200
224
External static pressure of the rated
air flow volume
150 Pa
180 Pa
200 Pa
100 Pa
120 Pa
130 Pa
60 Pa
75 Pa
75 Pa
A
°
°
1
5
6
2
1
4
1
3
1
4
NOTE:
Failure to set this parameter may result in
decreased air
fl
ow and condensation.
1. Press and hold down the , and buttons
simultaneously for 4 or more seconds. ( , the
Unit No., Item Code and Detailed Data will blink on
the LCD display.)
2. The indoor unit numbers in the group control will be
sequentially displayed whenever the Unit Select button
is pressed .
Only the fan motor for the selected indoor unit will operate
during this time.
3. Specify the “ ” item code by pressing the
buttons for the temperature setting buttons and confirm
the values. (“ ” set at shipment)
4. Press the buttons for the time to amend the
values for the set data. See Table 1-11-2-2-3 and
Fig. 1-11-2-2-4 and select a value “ ”, “ ” or
“ ”.
5. Press the button.
The display will stop blinking and remain illuminated.
6. Press the button. The fan motor will stop operating
and the LCD display will return to the normal stop mode.
/
/
/
/
1
ON
TP6
TP3
TP1
2
SW001
3
1
TP6
TP3
TP1
2
SW001
3
ON
Indoor Unit control PC board
Setting at
shipment
Fig. 1-11-2-2-3
1-2. Operating the Timer Remote Controller (CZ-RTC4)
How to set the external static pressure
SM830277-00_大洋州向け R32シングル_TD&SM.indb 8
2019/02/27 11:51:08
Summary of Contents for S-160PE1R5B
Page 12: ...MEMO Xi SM830277 00_ R32 _TD SM indb 12 19 02 26 9 34 28...
Page 136: ...MEMO 2 16 SM830277 00_ R32 _TD SM indb 16 19 02 28 13 25 27...
Page 164: ...MEMO 4 22 SM830277 00_ R32 _TD SM indb 22 19 02 21 11 54 26...
Page 202: ...MEMO 5 38 SM830277 00_ R32 _TD SM indb 38 19 02 28 13 37 39...
Page 274: ...201903 SM830277 00_ R32 _TD SM indb 1 19 02 12 9 03 53...