2
2-11
Display of remote controller
Display During Auto Address Setting
On the surface of outdoor unit control P.C. board
1 2
LED
Blinks alternately
* Do not short circuit the A.ADD pin again during auto address setting.
LEDs 1 and 2 go out and address setting is interrupted.
* When auto address setting is normally completed, both LEDs 1 and 2 go out.
In other cases, correct settings referring to the following table and perform auto address setting again.
Contents of LEDs 1 and 2 on outdoor unit control P.C. board
: Illuminating
: Blinking
: Go out
LED 1
LED
C
2
ontents of display
After turned ON power (not during auto address setting), it is entirely impossible to communicate with the
indoor unit in the system.
After turned ON power (not during auto address setting), although the indoor units more than 1 unit in the
system are recognized, there are inconsistencies between the number of indoor units and setting number of
indoor units.
Under auto address setting
Alternately
Auto address setting completed
There are inconsistencies between the number of indoor units and setting number of indoor units.
(at the time of auto address setting)
Simultaneously
Alternating
4
C
T
R
-
Z
C
Blinking “
” indicator
Cancel
Auto address
1
Assigning
Request concerning recording the indoor/outdoor unit combination numbers.
After auto address setting has been completed, be sure to record them for future reference.
List the outdoor main unit system address and the addresses of the indoor units in that system in an easily visible location (next
to the nameplate), using a permanent marking pen or similar means that cannot be abraded easily.
Example: (Outdoor) 1 - (Indoor) 1-1, 1-2, 1-3…
(Outdoor) 2 - (Indoor) 2-1, 2-2, 2-3…
These numbers are necessary for later maintenance. Please be sure to indicate them.
60Bὒᕞࢩࣥࢢࣝኳᇙ60LQGE
Alarm display
After LED1 blinks M times, LED2 blinks N times.
This will be repeated.
Number of blinks
Type of alarm
N = number of alarm No.
M
2
Alarm P
3
Alarm H
4
Alarm E
5
Alarm F
6
Alarm L
For example: After LED1 blinks twice, LED2 blinks 16 times. This will be repeated.
The alarm shows “P16”.
( : Blink)
Connect the outdoor unit maintenance remote controller to the RC plug (3P, BLU) on outdoor main unit control
P.C. board and make confirmation.
CZ-RTC5B
SM830277-00_大洋州向け R32シングル_TD&SM.indb 11
19/02/28 13:25:26
Summary of Contents for S-160PE1R5B
Page 12: ...MEMO Xi SM830277 00_ R32 _TD SM indb 12 19 02 26 9 34 28...
Page 136: ...MEMO 2 16 SM830277 00_ R32 _TD SM indb 16 19 02 28 13 25 27...
Page 164: ...MEMO 4 22 SM830277 00_ R32 _TD SM indb 22 19 02 21 11 54 26...
Page 202: ...MEMO 5 38 SM830277 00_ R32 _TD SM indb 38 19 02 28 13 37 39...
Page 274: ...201903 SM830277 00_ R32 _TD SM indb 1 19 02 12 9 03 53...