Troubleshooting by Indication on the Remote Controller
Mini UM S/M
132
Troubleshooting
4.24
“
J6
”
Outdoor Unit: Malfunction of Thermistor (R4T) for
Outdoor Unit Heat Exchanger
Remote
Controller
Display
J6
Applicable
Models
AII outdoor unit models
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the heat exchanger thermistor.
Malfunction
Decision
Conditions
When a short circuit or an open circuit in the heat exchange thermistor is detected.
Supposed
Causes
Defect of thermistor (R4T) for outdoor unit heat exchanger
Defect of outdoor unit PC board (A1P)
Troubleshooting
∗
Refer to thermistor resistance / temperature characteristics table on P190.
(V3074)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Resistance
is normal when
measured after
disconnecting the thermistor
R4T from the outdoor
unit PC board.
(3.5k
Ω
~
360k
Ω
)
Replace outdoor unit PC board
A1P.
Connect the thermistor and turn
on again.
NO
NO
Replace the thermistor R4T.
YES
YES
Connector
is connected to outdoor
unit PC board
(A1P).
Mini UM.book Page 132 Monday, January 24, 2005 11:32 AM