Mini UM S/M
List of Malfunction Code
Troubleshooting
101
Outdoor
Unit
LA
9
9
9
Malfunction of power unit
—
LC
9
9
9
Malfunction of transmission between inverter and
control PC board
140
P1
9
9
9
Inverter over-ripple protection
—
P4
9
9
9
Malfunction of inverter radiating fin temperature rise
sensor
142
PJ
9
9
9
Faulty combination inverter and fan driver,
Malfunction of capacity setting
143
System
U0
8
7
9
Low pressure drop due to refrigerant shortage or
electronic expansion valve failure
144
U1
9
9
9
Reverse phase / open phase
—
U2
9
9
9
Power supply insufficient or instantaneous failure
145
U3
9
9
9
Check operation is not conducted.
147
U4
9
9
9
Malfunction of transmission between indoor and
outdoor units
148
U5
9
9
9
Malfunction of transmission between remote
controller and indoor unit
150
U5
7
8
7
Failure of remote controller PC board or setting
during control by remote controller
—
U7
9
9
9
Malfunction of transmission between outdoor units
—
U8
9
9
7
Malfunction of transmission between master and
slave remote controllers (malfunction of slave remote
controller)
151
U9
9
9
9
Malfunction of transmission between indoor unit and
outdoor unit in the same system
152
UA
9
9
9
Excessive number of indoor units etc.
154
UC
8
8
8
Address duplication of central remote controller
155
UE
9
9
9
Malfunction of transmission between central remote
controller and indoor unit
156
UF
9
9
9
Refrigerant system not set, incompatible wiring /
piping
158
UH
9
9
9
Malfunction of system, refrigerant system address
undefined
159
Central-
ized
Control
and
Schedule
Timer
UE
9
9
9
Malfunction of transmission between centralized
remote controller and indoor unit
160
M1
8
or
7
9
9
PC board defect
161
M8
8
or
7
9
9
Malfunction of transmission between optional
controllers for centralized control
162
MA
8
or
7
9
9
Improper combination of optional controllers for
centralized control
163
MC
8
or
7
9
9
Address duplication, improper setting
165
Heat
Reclaim
Ventila-
tion
64
8
7
9
Indoor unit’s air thermistor error
—
65
8
7
9
Outside air thermistor error
—
68
8
7
9
Malfunction of HVU
—
6A
8
7
9
Damper system alarm
—
6A
9
9
9
Damper thermistor error
—
6F
8
7
9
Malfunction of simple remote controller
—
6H
8
7
9
Malfunction of door switch or connector
—
94
9
9
9
Internal transmission error
—
9
: Blink
8
: ON
7
: OFF
Malfunction
code
Operation
lamp
Inspection
display
Unit No.
Malfunction contents
Page
Referred
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
Mini UM.book Page 101 Monday, January 24, 2005 11:32 AM