Special Control
Mini UM S/M
44
Function
3.7
Pressure Equalization Prior to Startup
Before activating the compressor, the activation load is lightened by equalization across the
compressor. In addition, inverters turn on electricity and capacitors are charged.
Actuator
Operation
Remarks
Compressor
OFF
Outdoor unit fan
Cooling:OFF
Heating:Ta>26˚C; STEP8,
Ta
≤
26˚C; OFF
Four way valve
Keep former condition.
Main electronic expansion valve
(EV1)
0 pls
Subcooling electronic expansion
valve (EV2)
0 pls
Hot gas bypass valve (SVP)
ON
Receiver gas discharging valve
(SVG)
OFF
Ending conditions
•
•
3 min.
•
•
Pc-Pe<0.2 MPa
or