Mini UM S/M
Troubleshooting by Indication on the Remote Controller
Troubleshooting
127
∗
1 Coil check method for the moving part of the electronic expansion valve
Disconnect the electronic expansion valve from the PC board and check the continuity between
the connector pins.
(Normal)
: Continuity Approx. 300
Ω
: Continuity Approx. 150
Ω
×
: No continuity
Pin No.
1. White
2. Yellow
3. Orange
4. Blue
5. Red
6. Brown
1. White
×
×
×
2. Yellow
×
×
3. Orange
×
×
4. Blue
×
5. Red
×
6. Brown
Mini UM.book Page 127 Monday, January 24, 2005 11:32 AM