Mini UM S/M
Specifications
Specifications
9
Ceiling Mounted Cassette Type (Multi Flow) 600
×
600
Notes:
1 Indoor temp. : 27˚CDB, 19.5˚CWB / outdoor temp.: 35˚CDB / Equivalent piping length: 7.5m,
level difference: 0m.
2 Indoor temp. : 27˚CDB, 19.0˚CWB / outdoor temp.: 35˚CDB / Equivalent piping length: 7.5m,
level difference: 0m.
3 Indoor temp. : 20˚CDB / outdoor temp.: 7˚CDB, 6˚CWB / Equivalent piping length; 7.5m,
level difference; 0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
Model
S-40YM3HPS
S-50YM3HPS
1 Cooling Capacity (19.5˚CWB)
kcal/h
4,000
5,000
Btu/h
15,900
19,900
kW
4.7
5.8
2 Cooling Capacity (19.0˚CWB)
kW
4.5
5.6
3 Heating Capacity
kcal/h
4,300
5,400
Btu/h
17,000
21,500
kW
5.0
6.3
Casing
Galvanized Steel Plate
Galvanized Steel Plate
Dimensions: (H
×
W
×
D)
mm
260 (286)
×
575
×
575
( ): Include Control Box
260 (286)
×
575
×
575
( ): Include Control Box
Coil (Cross
Fin Coil)
Rows
×
Stages
×
Fin Pitch
mm
2
×
10
×
1.5
2
×
10
×
1.5
Face Area
m
2
0.269
0.269
Fan
Model
QTS32C15M
QTS32C15M
Type
Turbo Fan
Turbo Fan
Motor Output
×
Number
of Units
W
55
×
1
55
×
1
Air Flow Rate (H/L)
m
3
/min
11/8
14/10
cfm
388/282
494/353
Drive
Direct Drive
Direct Drive
Temperature Control
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Sound Absorbing Thermal Insulation Material
Foamed Polystyrene/Foamed
Polyethylene
Foamed Polystyrene/Foamed
Polyethylene
Piping
Connections
Liquid Pipes
mm
φ
6.4 (Flare Connection)
φ
6.4 (Flare Connection)
Gas Pipes
mm
φ
12.7 (Flare Connection)
φ
12.7 (Flare Connection)
Drain Pipe
mm
VP20
External Dia. 26
Internal Dia. 20
VP20
External Dia. 26
Internal Dia. 20
Machine Weight
kg
18
18
5 Sound Level (H/L) (230V)
dBA
36/28
41/33
Safety Devices
Fuse
Fuse,
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Connectable outdoor unit
R410A Series
R410A Series
Decoration
Panels
(Option)
Model
CZ-02KPY11P
CZ-02KPY11P
Panel Color
White (Ral 9010)
White (Ral 9010)
Dimensions: (H
×
W
×
D)
mm
55
×
700
×
700
55
×
700
×
700
Air Filter
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Weight
kg
2.7
2.7
Standard Accessories
Operation Manual, Installation Manual,
Paper Pattern for Installation, Drain
Hose, Clamp Metal, Washer Fixing
Plate, Sealing Pads, Clamps, Screws,
Washer for Hanging Bracket,
Insulation for Fitting.
Operation Manual, Installation Manual,
Paper Pattern for Installation, Drain
Hose, Clamp Metal, Washer Fixing
Plate, Sealing Pads, Clamps, Screws,
Washer for Hanging Bracket,
Insulation for Fitting.
Drawing No.
3D038929A
(
)
(
)
Conversion Formulae
kcal/h=kW
×
860
Btu/h=kW
×
3414
cfm=m
3
/min
×
35.3
Mini UM.book Page 9 Monday, January 24, 2005 11:32 AM