Mini UM S/M
Precautions for New Refrigerant (R410A)
Precautions for New Refrigerant (R410A)
201
9. Weigher for refrigerant charge
Specifications
2
High accuracy
TA101A (for 10-kg cylinder) = ± 2g
TA101B (for 20-kg cylinder) = ± 5g
2
Equipped with pressure-resistant sight glass to check liquid refrigerant charging.
2
A manifold with separate ports for HFCs and previous refrigerants is equipped as standard
accessories.
Differences
2
Measurement is based on weight to prevent change of mixing ratio during charging.
10. Charge mouthpiece
Specifications
2
For R410A, 1/4"
→
5/16" (2min
→
2.5min)
2
Material is changed from CR to H-NBR.
Differences
2
Change of thread specification on hose connection side (For the R410A use)
2
Change of sealer material for the HFCs use.
Mini UM.book Page 201 Monday, January 24, 2005 11:32 AM