Precautions for New Refrigerant (R410A)
Mini UM S/M
198
Precautions for New Refrigerant (R410A)
2. Torque wrench
Specifications
2
Dimension B
Unit:mm
No change in tightening torque
No change in pipes of other sizes
Differences
2
Change of dimension B
Only 1/2", 5/8" are extended
3. Vacuum pump with check valve
Specifications
2
Discharge speed
Maximum degree of vacuum
50 l/min (50Hz)
–100.7 kpa ( 5 torr – 755 mmHg)
60 l/min (60Hz)
2
Suction port UNF7/16-20(1/4 Flare)
UNF1/2-20(5/16 Flare) with adapter
Differences
2
Equipped with function to prevent reverse oil flow
2
Previous vacuum pump can be used by installing adapter.
Nominal size
Class-1
Class-2
Previous
1/2
24
26
24
5/8
27
29
27
Dimension B
For class-1: R407C
For class-2: R410A
Vacuum pump adapter
Reverse flow preventive
vacuum adapter
Mini UM.book Page 198 Monday, January 24, 2005 11:32 AM