Mini UM S/M
Field Setting
Test Operation
81
3.3
Detail of Setting Mode
3.3.1 Cool / Heat Mode Switching
There are the following 2 cool/heat switching modes.
Set cool/heat separately for each outdoor unit system by indoor unit remote controller.
Set cool/heat separately for each outdoor unit system by cool/heat switching remote
controller.
Set Cool/Heat Separately for Each Outdoor System by Indoor Unit Remote Controller
It does not matter whether or not there is outdoor - outdoor unit wiring.
Set outdoor unit PC board DS1-1 to “indoor” (factory set).
Set cool/heat switching to “individual” for “Setting mode 1” (factory set).
MODE
H1P
H2P
H3P
H4P
H5P
H6P
H7P
IND
SLAVE
L.N.O.P. DEMAND
MASTER
C/H SELECT
C/H SELECT
C/H SELECT R.C.
Indoor unit
Indoor unit
(V3163)
I-O
O-O
Dip SW.
DS1-1
O
A
B
C
F1
F1
F2
F1
F2
F2
F1
F2
I
TEST
MALFNC.