9.42
5.30
3.40
2.36
1.34
0.849
0.491
12.0
13.5
16.0
17.0
19.0
23
28
1.5
1.5
1.5
1.5
1.5
1.6
1.8
0.8
0.8
1.0
1.0
1.0
1.2
1.2
1.8
2.4
3.0
3.6
4.4
5.5
7.3
7/0.6
7/0.8
7/1.0
7/1.2
2
3.5
5.5
8
14
22
38
Conductor
Structure
or
shape
(wires/mm
2
)
Outside
diameter
(mm)
Insulation
thickness
(mm)
Sheath
thickness
(mm)
(Reference)
Finish O.D.
(mm)
Max.
conductor
resistance
(20
°
C)
(W/km)
Test
voltage
(V/1 min.)
Minimum
insulation
resistance
(MW
•
km)
(Reference)
Approx.
mass
(kg/km)
Nominal
cross
section
(mm
2
)
Circular
compression
Circular
compression
Circular
compression
Caution
Note
• Recommended eco-cable
Wire category: -conductor polyethylene-insulated power cable with heat-resistant
polyethylene sheath (Standard: EM JIS C 605)
Maximum permissible temperature: 90°C
Shield will increase finish outside diameter by approx. 1 mm.
• Appropriate cable should be selected to have sufficient allowance for parameters such
as operating ambient temperature and current.
• Current reduction coefficient, fundamental permissible current, etc., stated on this page
are subject to change due to e.g. standard revision. Consult cable manufacturers for
the latest information.
0.70
0.63
0.56
0.49
0.43
0.39
0.34
Up to 3
4
5 or 6
7 to 15
16 to 40
41 to 60
61 or more
No. of wires in a tube Coefficient
•Current reduction coefficient
5. Installation
Driver
Related page
• P.1-15 “Junction cable for motor”
<Supplement>
• The current correction coefficient is determined using the following formula:
(Max. permissible temp. – ambient temp.) ÷ 30
The current correction coefficient is determined according to the cable. Check the specifi
-
cation of the cable used.
• The current reduction coefficient is provided for the
case where the cable (-conductor cable in the case of
example), is housed in plastic race/sheath, plastic tube,
metal race/sheath, metal tube or flexible conduit.
Because the neutral conductor is not counted as a wire, the
current reduction coefficient for “3 or less” is applied as indi
-
cated by ( ) in the table right.