1-7-4
1
1
1-7-2. Operating the High-spec Wired Remote
Controller (CZ-RTC5A / CZ-RTC5B)
START
[
]
20:30 (THU)
How to set the external static pressure
Table 1-7-2 Setting the external static pressure
1. Keep pressing the
,
and
buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the LCD
display.
2. Press the
or
button to see each menu.
If you wish to see the next screen instantly, press the
or
button.
Select “8. Detailed settings” on the LCD display and press
the
button.
The “Detailed settings” screen appears on the LCD display.
Select the “Unit no.” by pressing the
or
button for changes.
3. Select the “Code no.” by pressing the
or
button.
Change the “Code no.” to “B0” by pressing the
or
button (or keeping it pressed).
4. Select the “Set data” by pressing the
or
button.
Select one of the “Set data” among “0001” – “0015”
according to the desired external static pressure setting by
pressing the
or
button.
Then press the
button.
(See the table below.)
When setting to auto airflow volume control:
Select the setting data to “-002”.
Then press the
button.
Indoor unit type
Item code
60, 71
100, 125, 140
B0
External static pressure of the rated
airflow volume (Pa)
150
150
0015
140
140
0014
130
130
0013
120
120
0012
100
110
0011
70
100
0008
60
70
0006
50
50
0005
30
30
0003
10
10
0001
No auto airflow volume setting
-001
Auto airflow volume setting
-002
5. Select the “Unit no.” by pressing the
or
button and press the
button.
The “Exit detailed settings and restart?” (Detailed setting-
end) screen appears on the LCD display.
Select “YES” and press the
button.
When the setting is completed, perform the test run for the
external static pressure setting described in “Auto External
Static Pressure Setting Operation”.
Auto External Static Pressure Setting Operation
6. Keep pressing the
,
and
buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the LCD
display.
7. Press the
or
button to see each menu.
If you wish to see the next screen instantly, press the
or
button.
Select “4. Test run” on the LCD display and press the
button.
The “Test run” screen appears on the LCD display.
Change the display from OFF to ON by pressing the
or
button. Then press the
button.
The “Maintenance func” screen appears on the LCD
display.
8. Press the
button. “TEST” will be displayed on the
LCD display.
9. Press the
button. Test run will be started.
Test run setting mode screen appears on the LCD display.
10. Set the operation mode to “
” and fan speed mode to
“
” by pressing the
or
button or
or
button. Then press the
button.
The fan motor will be activated, the auto external static
pressure setting operation and setting-check operation will
be performed for about 3 to 30 minutes.
The fan speed will change automatically while these
operations are in progress. When these operations
completed, “TEST” will be disappeared from the LCD
display.
NOTE:
The auto external static pressure setting operation
and setting-check operation will not be performed
unless “
(MODE FAN)” and “
(FAN
SPEED)” have been selected.
11. Press the
button.
The LCD display will be returned to the initial screen.
NOTE:
Failure to set this parameter may result in decreased
airflow and condensation.
SM830266-00_大洋州向けR32シングルTD&SM.indb 4
18/03/29 10:19:44
Summary of Contents for Inverter R32 Series
Page 93: ...1 10 10 1 SM830266 00_ R32 TD SM indb 10 18 03 29 10 19 58...
Page 94: ...1 10 11 1 SM830266 00_ R32 TD SM indb 11 18 03 29 10 19 58...
Page 95: ...1 10 12 1 SM830266 00_ R32 TD SM indb 12 18 03 29 10 19 59...
Page 96: ...1 10 13 1 SM830266 00_ R32 TD SM indb 13 18 03 29 10 20 00...
Page 241: ...MEMO 1 13 11 SM830266 00_ R32 TD SM indb 11 18 03 29 10 21 37...