
2
2
2-12
Abnormal
display
Wireless remote
controller
receiver display
Alarm contents
Error location
Operation
Timer
Standby
Outdoor Unit
P13
Timer and
st
andby
la
mp blinking
al
ternately
• Valve error
• Refrigerant circuit error.
• Wrong installation for refrigerant piping and wiring
• Valve blockage
• Check the refrigerant circuit
• Check the refrigerant piping and wiring installation
P14
• O
2
sensor detected
• Input from the O
2
sensor
P15
Operating
and
st
andby
lamp
blinking
alternately
• Insufficient gas level detected
• Check the refrigerant cycle (gas leak)
• Trouble with the electronic expansion valve
• Valve (or refrigerant circuit) blockage
P16
• Compressor overcurrent trouble
• Layer short on the compressor
• Compressor locked
• Check the outdoor unit control PCB
P22
• Outdoor unit fan motor trouble
• Outdoor unit fan trouble
• Check the outdoor unit fan motor
• Check the outdoor unit control PCB
P29
• Inverter compressor trouble
• Layer short on the compressor
• Check the outdoor unit control PCB
• Check the inverter compressor wiring (Open phase/
Reverse phase)
• Compressor actuation failure (include lock)
• Valve (or refrigerant circuit) blockage
P31
• Indoor unit in group control trouble
• Repair indoor unit which blinking alarm
2
-11. Auto address setting from the outdoor unit
●
If the power can be turned ON separately for the indoor and outdoor units in each system:
The indoor unit addresses can be set without running the compressor.
●
Be sure to use a jig for short-circuiting.
(1) Turn on the indoor and outdoor unit power for refrigerant system 1.
Short-circuit the A.ADD pin.
↓
Communication for auto address setting begins.
↓
LED 1 and 2 on the outdoor unit control PCB blink alternately, and turn OFF when address setting is completed.
↓
<Approximately 4 – 5 minutes are required.>
(2) Next, turn ON the power only at the indoor and outdoor units in a different system. Short-circuit the A.ADD pin.
↓
LED 1 and 2 on the outdoor unit control PCB blink alternately, and turn OFF when address setting is completed.
↓
Repeat the same procedure for each system and complete auto address setting.
↓
(3) Operation using the remote controller is now possible.
ON:
Blinking:
OFF:
01_301769_2WAY_eng.indb 39
2018/3/20 9:15:16
2-12. Test run using the indicator of the indoor unit (Type K2)
(1) Press and hold [Emergency Operation] button of the indoor unit for four
seconds or more.
(2) Then the lamps on the display will blink one after another.
(3) Release the button and again press and hold [Emergency Operation] button
for four seconds or more.
(4) All indicator lamps on the display blink while test run is in progress.
(5) Temperature control is not possible during the test run.
(6) If normal operation is not possible, the lamps on the display will indicate the problem.
See the section 2-10.
(7) After the test run is completed, press [Emergency Operation] button and confirm that
Emergency button
Indicator
the indicator lamps stop blinking.(A 60-minute automatic OFF timer function is included
in order to prevent continuous test run.)
2-13
. Caution for Pump Down
Pump down means refrigerant gas in the system is returned to the outdoor unit. Pump down is used when the unit is to be moved, or
before servicing the refrigerant circuit.
CAUTION
●
This outdoor unit cannot collect more than the rated refrigerant amount as shown by the nameplate on the back.
●
If the amount of refrigerant is more than that recommended, do not conduct a pump down. In this case use another
refrigerant collecting system.
●
Pay a special attention to the rotating of the fan while operating.
How to perform Pump-Down (Refrigerant recovery) properly
(1) Stop operation of the unit (cooling, heating etc.).
(2) Connect the pressure gauge to the service port of the gas tubing valve.
(3) Short-circuit the “PUMPDOWN” pin on an outdoor unit control PCB (CR) for
more than 1 second to release.
• Pump-Down begins and the unit starts operating.
• During Pump-Down, LED1 blinks and LED2 is lit on an outdoor unit control
PCB (CR).
• “CHK” blinks on the remote controller.
(4) Fully close the liquid tubing valve 2-3 minutes later.
The Pump-Down will begin.
(5) When the pressure gauge drops to 0.1-0.2MPa, close the gas tubing valve
tightly and short-circuit the “PUMPDOWN” pin for more than 1 second to release.
That is the end of Pump-Down.
• When running for more than 10 minutes, it stops even if the Pump-Down is not completed.
Check the blocked state of the liquid side valve.
• It also stops when the “PUMPDOWN” pin is short-circuited during the operation.
* For compressor protection, do not operate to the point where the unit tubing side reaches negative pressure.
HOW TO INSTALL WIRELESS REMOTE CONTROLLER
N OT E
See section “8. HOW TO INSTALL THE WIRELESS REMOTE CONTROLLER RECEIVER”.
SERVICING
CAUTION
●
Any qualified person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate
from an industry-accredited assessment authority, which authorizes their competence to handle refrigerants safely in
accordance with an industry recognised assessment specification.
●
Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the
assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable
refrigerants.
●
Servicing shall be performed only as recommended by the manufacturer.
●
Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of
ignition is minimised. For repair to the refrigerating system, (2) to (6) shall be completed prior to conducting work on the system.
(1)
Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present
while the work is being performed.
(2)
All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in
confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the
area have been made safe by control of flammable material.
(3) The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware
of potentially toxic or flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with all
applicable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.
(4)
If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing
equipment shall be available to hand. Have a dry powder or CO
2
fire extinguisher adjacent to the charging area.
(
5) No person carrying out work in relation to a refrigeration system which involves exposing any pipe work shall use any sources
of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette
smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which
refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to
be surveyed to make sure that there are no flammable hazards or ignition risks. “No Smoking” signs shall be displayed.
Pay a special attention to the rotating
of the fan while operating.
LED1 LED2
PUMPDOWN
01_301769_2WAY_eng.indb 40
2018/3/20 9:15:16
SM830266-00_大洋州向けR32シングルTD&SM.indb 12
18/03/29 11:58:31
Summary of Contents for Inverter R32 Series
Page 93: ...1 10 10 1 SM830266 00_ R32 TD SM indb 10 18 03 29 10 19 58...
Page 94: ...1 10 11 1 SM830266 00_ R32 TD SM indb 11 18 03 29 10 19 58...
Page 95: ...1 10 12 1 SM830266 00_ R32 TD SM indb 12 18 03 29 10 19 59...
Page 96: ...1 10 13 1 SM830266 00_ R32 TD SM indb 13 18 03 29 10 20 00...
Page 241: ...MEMO 1 13 11 SM830266 00_ R32 TD SM indb 11 18 03 29 10 21 37...